INSP-Final | 10/3/2018 | 10/4/2018 | 10/3/2018 | A | DONE |
Troy Cobbley
|
|
|
Life safety passed. Exit modifications approved by State of Idaho.
|
DOC - Permit Finaled | | | 10/3/2018 | | DONE |
|
|
|
per troy cobbley
|
INSP-Final | 9/28/2018 | 10/1/2018 | 10/2/2018 | A | CANC |
Troy Cobbley
|
|
|
Not ready for inspection yet as plans are still in the review status.
>> Inspection requested via mobile web by Nacho
|
INSP-Final | 9/27/2018 | 9/27/2018 | 10/1/2018 | P | FAIL |
Troy Cobbley
|
|
|
Items 3, 4, 5, 9 and 10 still need corrected. Inspection was left open in hopes that it could be finaled after hours if issues had been resolved.
Phone #: 2088613810 >> Inspection requested via mobile web by Nacho
|
INSP-Final | 9/26/2018 | 9/27/2018 | 9/27/2018 | A | FAIL |
Troy Cobbley
|
|
|
1. As per plan reviewer comment the "Oxygen 107" shall meet IFC 5306.2.2 2. The security doors shall meet IFC 1010.1.9.6 get building code and fire code official approval. 3.Provide revised plans that show "Hall 122" exterior exit door being deleted and the exit sign at the double doors at "Hall 122". 4. Provide approval that locked gates at the east and west exits can remain. 5. Finish roadway and fire dept access. 6. Provide exit discharge light at west exit door. 7. Provide final for hood suppressioni permit. 8. Provide CO2 detection in Riser Room and at fire place. 9. Provide exit sign/exit discharge light as shown in the Dining Room and approved hardware. 10. Provide verification employees and visitors will be provided with exit door code.
Call prior to going Phone #: 2088613810 >> Inspection requested via mobile web by Nacho
|
INSP-Final | 9/25/2018 | 9/26/2018 | 9/27/2018 | A | FAIL |
Troy Cobbley
|
|
|
Todays inspection covered exit signs,emergency lights and fire extinguishers. Provide missing exit sign and exit discharge lighting
Call prior to going Phone #: 2088613810 >> Inspection requested via mobile web by Nacho
|