INSP-Sprinkler Rough-in/Hydro | 11/4/2019 | 11/4/2019 | 11/4/2019 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. No fire alarm.
John ###-####
|
DOC - Permit Finaled | | | 11/4/2019 | | DONE |
|
|
|
per troy cobbley
|
INSP-Conference | 7/16/2019 | 7/16/2019 | 7/16/2019 | P | DONE |
Troy Cobbley
|
|
|
I spoke with the owners rep from texas about the exit sign over the blocked secondary exit.
|
INSP-Final | 12/10/2018 | 12/10/2018 | 12/10/2018 | P | FAIL |
Troy Cobbley
|
|
|
Remove the exit sign as discussed at the blocked door.
Call prior to going Phone #: 8174129198 >> Inspection requested via mobile web by Ryan
|
INSP-Final | 12/7/2018 | 12/7/2018 | 12/7/2018 | P | FAIL |
Troy Cobbley
|
|
|
No city approved drawings or small documents on site. I noted that a marked exit has been blocked by a cooler in the Pick room.
Call prior to going Phone #: 8174129198 >> Inspection requested via mobile web by Ryan
|
INSP-Final | 9/4/2018 | 9/7/2018 | 9/7/2018 | P | FAIL |
Jim Page
|
|
|
No phone number provided for point of contact. Fire alarm notification required in area of work (any permit is required for any and all fire alarm modifications). Provide emergency lighting for the exterior at the emergency exit discharge landings per IFC section 1008.3.2.
>> Inspection requested via mobile web by Kenny
|