Permit Information
Permit NumberNAF19-00001
StatusIssued
Name IRIDIUM PROTECTION LLC
Site Address 2900 CHINDEN BLVD
Project NameGC/RIVERSIDE HOTEL RETRO-FIT
Customer Number 
ePlanReviewNo
Description
Retro-fit of (2- 9'-10" kitchen hoods), 1- system for appliance rearrangement. Ansul R102 system, 17 flow points total. No nozzle coverage behind filter bank or duct (water wash)***MAS***
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final1/25/20191/25/20191/25/2019PDONE
DetailsTroy Cobbley
permit finaled

Inspection requested via web by Eric Stanley
DOC - Permit Finaled  1/25/2019 DONE
Per Troy C
INSP-Sprinkler Rough-in/Hydro1/23/20191/24/20191/24/2019AFAIL
DetailsTroy Cobbley
No testing performed. Verification is needed that the Ansul suppression system is approved by Ansul to be installed, as is, in the Gaylord water wash hood.


Call prior to going Phone #: 2086317804 >> Inspection requested via mobile web by Nate