Permit Information
Permit NumberNAF19-00110
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 9655 W STATE ST
Project NameFOOTHILLS CHRISTIAN CHURCH
Customer Number 
ePlanReviewNo
Description
Relocate existing underground piping around new proposed building site.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final7/6/20207/7/20207/7/2020ADONE
DetailsTroy Cobbley
Permit finaled.

Nate Phone #: ###-#### Inspection requested via web by Nathan Stenquist
DOC - Permit Finaled  7/7/2020 DONE
Per Troy
INSP-Supply line flush11/19/201911/20/201911/20/2019APASS
DetailsTroy Cobbley
U.G. hydro test witnessed with no pressure loss at the guage.


Troy Nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
INSP-Supply line flush11/14/201911/15/201911/15/2019APASS
DetailsTroy Cobbley
The underground supply line flush was witnessed.

troy nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
INSP-Supply line flush11/13/201911/14/201911/14/2019APART
DetailsTroy Cobbley
The remaining underground supply piping is ok for cover. The flush was not ready due to waiting on a thrust block on unrelated piping at the crosss ; flush
Troy Nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
INSP-Supply line flush11/12/201911/13/201911/13/2019PPASS
DetailsTroy Cobbley
The underground tie-in from the PIV to the building passed. Piping can be covered.

troy nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist
INSP-Supply line flush11/11/201911/12/201911/12/2019APASS
DetailsTroy Cobbley
See the city approved plans for section of piping that is ok for cover.

UNDERGROUND COVER
TROY NELSON Phone #: ###-#### Inspection requested via web by Brodie Stenquist