INSP-Sprinkler Rough-in | 4/24/2020 | 4/24/2020 | 4/24/2020 | P | PASS |
Troy Cobbley
|
|
|
The remaining underground supply piping is ok for cover.
Call for access Phone #: 2084774515 >> Inspection requested via mobile web by Jeremiah
|
INSP-Sprinkler Rough-in | 3/27/2020 | 3/27/2020 | 3/27/2020 | A | PASS |
Troy Cobbley
|
|
|
The underground supply piping from the point of connection to with-in 5' of the building is ok for cover. Plans indicate 4" piping but 6" has been installed. Plans are to be resubmitted monday showing the actual installed pipe size as agreed.
Jeremiah - State Fire - ###-####
|