Final | 11/8/2001 | 11/8/2001 | 11/8/2001 | P | PASS |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 11/08/2001 at 09:02:24. Contact: ###-####.
|
Groundwork | 10/10/2001 | 10/10/2001 | 10/10/2001 | P | FAIL |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 10/10/2001 at 08:02:04. Contact: ###-####. test failed on D.W.V. water test ok need to protect pipe passing through concret at base of break sink called contractor 10/10/2001 3:02:38 PM
|
Groundwork | 10/10/2001 | 10/10/2001 | 10/10/2001 | P | PASS |
Jim Johnson
|
|
|
Scheduled by Inspector: 360 On 10/10/2001 3:04:34 PM ground work and wall rough-in drains and vent,s and water ok 10/10/2001 4:33:34 PM
|
Groundwork | 10/9/2001 | 10/9/2001 | 10/9/2001 | P | FAIL |
Jim Johnson
|
|
|
###-#### need to hang vent piping every 4 feet. need cleanout on break sink also need to protect piping passing through concret. need to change combo to san tee for floor drain ( upc 1002.4 vent opening below weir of trap ) need to change pvc pipe gluded in to abs fitting to abs pipe on 4x6 abs combo called plumbing contractor about correction,s 10/9/2001 3:34:53 PM
|