Final | 2/17/2003 | 2/18/2003 | 2/18/2003 | A | PASS |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 2/17/2003 at 11:07:57 AM.
|
Med/Gas Systems | 2/11/2003 | 2/12/2003 | 2/12/2003 | A | PART |
Jim Johnson
|
|
|
24 hr pressure test on vacuum line test ok 2/12/2003 9:20:11 AM
|
Med/Gas Systems | 2/10/2003 | 2/11/2003 | 2/11/2003 | A | PART |
Jim Johnson
|
|
|
###-#### start of 24 hr. pressure test on vacuum line from 5th floor to mech. room 2/11/2003 9:42:16 AM
|
Plumbing Rough-in | 1/22/2003 | 1/23/2003 | 1/23/2003 | A | PART |
Jim Johnson
|
|
|
sharon--partail med gas ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie start of 24 hr. pressure test on main vacuum line from 5th floor to mech. room 1/23/2003 9:39:46 AM
|
Plumbing Rough-in | 1/15/2003 | 1/15/2003 | 1/15/2003 | P | PART |
Jim Johnson
|
|
|
sharon; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie under floor drain piping in room,s 547 and 548 test ok 1/16/2003 11:13:47 AM
|
Plumbing Rough-in | 1/9/2003 | 1/10/2003 | 1/10/2003 | A | PART |
Jim Johnson
|
|
|
###-#### under floor piping for drain,s for room 544 and 543 test ok 1/10/2003 11:07:12 AM
|
Plumbing Rough-in | 1/7/2003 | 1/8/2003 | 1/8/2003 | A | PART |
Jim Johnson
|
|
|
in wall water and drain line,s test ok 1/8/2003 3:26:13 PM
|
Plumbing Rough-in | 1/6/2003 | 1/7/2003 | 1/7/2003 | P | PART |
Jim Johnson
|
|
|
sharon; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie start of med gas pressure test on on main system in wall,s and down main hall 1/7/2003 3:20:12 PM
|
Plumbing Rough-in | 12/26/2002 | 12/27/2002 | 12/27/2002 | A | PART |
Jim Johnson
|
|
|
###-#### under floor drain piping for room 527 test ok ok to cover 12/27/2002 10:59:14 AM
|
Plumbing Rough-in | 12/17/2002 | 12/17/2002 | 12/17/2002 | P | PART |
Jim Johnson
|
|
|
PARTIAL; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung under floor drains on bathroom group in south west corner test ok 12/17/2002 5:13:19 PM
|
Plumbing Rough-in | 12/9/2002 | 12/9/2002 | 12/9/2002 | P | PART |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Amy Lawson test on room,s 528 &526 D.W.V. test ok test for water and D.W.V in room 592 test ok 12/9/2002 6:26:40 PM
|
Plumbing Rough-in | 12/5/2002 | 12/6/2002 | 12/6/2002 | A | PART |
Jim Johnson
|
|
|
SHARON; Phone #: ###-#### Internet Inspection Request from: Darla Downs water in room,s 526&528 test ok need to retest D.W.V. test failed in room,s 526&528 12/6/2002 2:38:29 PM
|
Med/Gas Systems | 11/26/2002 | 11/26/2002 | 11/26/2002 | P | PART |
Jim Johnson
|
|
|
24 hour pressure test on med gas and vacuum in main hall testok 11/26/2002 1:43:35 PM
|
Plumbing Rough-in | 11/22/2002 | 11/25/2002 | 11/25/2002 | A | PART |
Jim Johnson
|
|
|
sherin --water and med gas; Phone #: ###-#### Internet Inspection Request from: Linda Hartwell main water lines in hall test ok start of pressure test of med gas and vav in maines in hall 11/25/2002 2:55:02 PM
|
Plumbing Rough-in | 11/12/2002 | 11/13/2002 | 11/13/2002 | P | PART |
Jim Johnson
|
|
|
sharon; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie under floor drain piping fro room,s 528&529 test ok 11/13/2002 4:52:22 PM
|
Plumbing Rough-in | 10/28/2002 | 10/29/2002 | 10/29/2002 | A | PART |
Jim Johnson
|
|
|
partial ###-#### rough-in plumbing for room,s 547&548 test ok 10/29/2002 10:35:00 AM
|
Plumbing Rough-in | 10/25/2002 | 10/28/2002 | 10/28/2002 | A | PART |
Jim Johnson
|
|
|
SHARON; Phone #: ###-#### Internet Inspection Request from: Darla Downs waste test in room,s 546 & 545 test ok med gas for room,s 543,542 & 541 pressure test ok 10/28/2002 11:27:40 AM
|
Plumbing Rough-in | 10/25/2002 | 10/25/2002 | 10/25/2002 | P | PART |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Amy Lawson rough-in waste for room,s 543,544,545&546 test ok 10/25/2002 2:51:08 PM
|
Med/Gas Systems | 10/23/2002 | 10/24/2002 | 10/24/2002 | A | NR |
Jim Johnson
|
|
|
|
Plumbing Rough-in | 10/23/2002 | 10/24/2002 | 10/24/2002 | A | PART |
Jim Johnson
|
|
|
###-#### rough-in plumbing in room,s 541& 542 waste and water test ok test on water only in room,s 543,544,545 & 546 test ok 10/24/2002 11:10:23 AM
|
Med/Gas Systems | 10/10/2002 | 10/11/2002 | 10/11/2002 | A | PART |
Jim Johnson
|
|
|
pressure test on med gas in room,s 544,545,546 and 547 test ok 10/11/2002 10:35:37 AM
|
Med/Gas Systems | 10/9/2002 | 10/10/2002 | 10/10/2002 | A | PART |
Jim Johnson
|
|
|
###-#### start of presure test on room,s 544 545, 546 and 547 10/10/2002 10:13:26 AM
|
Plumbing Rough-in | 10/7/2002 | 10/7/2002 | 10/7/2002 | P | PART |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung room,s 530&531 drain,s waste and vent,s test ok 10/7/2002 3:12:01 PM
|
Plumbing Rough-in | 10/3/2002 | 10/4/2002 | 10/4/2002 | P | PART |
Jim Johnson
|
|
|
###-#### med gas from room to main hall in room,s 530, 529, 548 and main valves at room 588 pressure test ok rough-in on room,s 532 and 533 water and waste test ok test on water only in room,s 530&531 test ok 10/4/2002 3:52:07 PM
|
Med/Gas Systems | 10/3/2002 | 10/3/2002 | 10/3/2002 | P | PART |
Jim Johnson
|
|
|
###-#### start of 24 hr pressure test 10/3/2002 3:11:13 PM
|
Med/Gas Systems | 9/30/2002 | 10/1/2002 | 10/1/2002 | A | PART |
Jim Johnson
|
|
|
pressure test for med gas in room,s stub out ot main hall test ok ( room,s 534 533 532 & 531) 10/1/2002 11:45:38 AM
|
Plumbing Rough-in | 9/27/2002 | 9/30/2002 | 9/30/2002 | A | PART |
Jim Johnson
|
|
|
sharon & med gas; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie start of pressure test for med gas on room,s 531,532,533 and534. rough-in on plumbing in room,s 535 ,582 584 585 587 and 578 test ok 9/30/2002 12:04:28 PM
|
Med/Gas Systems | 9/25/2002 | 9/26/2002 | 9/26/2002 | P | PART |
Jim Johnson
|
|
|
med gas for room,s 539,537,536and 535 from room stub in to main hall pressure test ok 9/26/2002 2:52:33 PM
|
Plumbing Rough-in | 9/25/2002 | 9/25/2002 | 9/25/2002 | P | PART |
Jim Johnson
|
|
|
medgas pres test sharon; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie start of med gas pressure test 9/25/2002 3:52:04 PM
|
Plumbing Rough-in | 9/20/2002 | 9/23/2002 | 9/23/2002 | A | PART |
Jim Johnson
|
|
|
SHARON; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie-- ALSO PRESSURE TEST???? pressure test on med gas test ok water and drain,s and vent,s on north west corner test ok 9/23/2002 10:51:59 AM
|
Plumbing Rough-in | 9/19/2002 | 9/19/2002 | 9/19/2002 | P | PART |
Jim Johnson
|
|
|
pressure test-medical gas st al's 5th floor-sharon ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie start of rough pressure test 9/19/2002 3:22:58 PM
|
Plumbing Rough-in | 9/11/2002 | 9/11/2002 | 9/11/2002 | P | PART |
Jim Johnson
|
|
|
###-#### north side bathroom group air test ok 9/11/2002 4:09:11 PM
|
Plumbing Rough-in | 8/22/2002 | 8/22/2002 | 8/22/2002 | P | PART |
Jim Johnson
|
|
|
SHARON; Phone #: ###-#### 8/22/2002 6:35:34 PM
|
Plumbing Rough-in | 8/19/2002 | 8/20/2002 | 8/20/2002 | A | PART |
Jim Johnson
|
|
|
PARTIAL\\###-#### bathroom group on north-west side under floor piping test ok 8/20/2002 2:58:28 PM
|
Plumbing Rough-in | 8/16/2002 | 8/16/2002 | 8/16/2002 | P | PART |
Jim Johnson
|
|
|
###-#### bathroom area,s on northwest side of 5th floor of south tower under floor drain,s test ok 8/16/2002 4:32:01 PM
|