Final | 4/24/2003 | 4/25/2003 | 4/25/2003 | A | PASS |
Lee Rice
|
|
|
charles; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Plumbing Rough-in | 2/24/2003 | 2/24/2003 | 2/24/2003 | P | PASS |
Bill VanDegrift
|
|
|
###-#### charles ri ok 2/24/2003 2:02:33 PM
|
Plumbing Rough-in | 2/20/2003 | 2/21/2003 | 2/21/2003 | A | CANC |
Bill VanDegrift
|
|
|
###-####
|
Plumbing Rough-in | 2/21/2003 | 2/21/2003 | 2/21/2003 | P | FAIL |
Bill VanDegrift
|
|
|
remove rubber tees at lav and tub is s-trapped 2/21/2003 2:48:24 PM
|
Plumbing Rough-in | 2/10/2003 | 2/11/2003 | 2/11/2003 | A | FAIL |
Bill VanDegrift
|
|
|
CHARLES 1-###-#### waste and water to washer must be protected from freezing, repipe wc waste and vent use approved fittings and transittion couplings, vent tub trap, remove black iron pipe in water to tub, remove compression fittings in water at tub and replace with crimps, pex must not be with in 18"of water heater, provide shutoff valve, pipe t&p and required water heater pan drain to a sump with a pump that will handle discharge from t&p drain apx25 gpm, replace old t&p drain. 2/11/2003 9:54:58 AM
|