Permit Information
Permit NumberPLM03-00696
StatusFinaled
Name INSELMAN PLUMBING CO
Site Address 1745 N FIVE MILE RD
Project NameSpeedy Clean Car Wash
Customer Number 
ePlanReview 
Description
Water, waste lines and fixtures, sand and grease interceptor per initial cert of value $29,173.00//06/19/03 final cert $29,704.00
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/16/20036/16/20036/16/2003PPASS
DetailsJim Johnson
Scheduled by a contractor via Hello! on 6/16/2003 at 9:37:00 AM. Contact: ###-####. 6/16/2003 5:01:07 PM
Final6/11/20036/11/20036/11/2003PPART
DetailsJim Johnson
need to be corrected for final 1- provide a R.P. for make-up water to boiler 2-need to provide access and clearance for existing R.P. need to move out away from wall for maintenance and repair 3- need to provide identification sign,s for hydrant,s on west side of building and in north wash bay as potable water 4- may need to provide a non-potable water source for pressure washer 6/11/2003 4:47:19 PM
Final6/6/20036/6/20036/6/2003PPART
DetailsJim Johnson
had to reschedule with Bill and Lee for walk through on 6-10-03 oked temp 6/6/2003 12:31:32 PM
Final5/29/20035/30/20035/30/2003APART
DetailsJim Johnson
Scheduled by a contractor via Hello! on 5/29/2003 at 1:57:28 PM. Contact: ###-####. additional cross control connection may be required for the make up water for the boiler have schedule a walk through with Bill with united water and Lee Rice for the 2 or 3 of june 5/30/2003 4:40:48 PM
Water and/or Sewer4/3/20034/4/20034/4/2003APASS
DetailsJim Johnson
water line only ###-####- patty
Groundwork3/25/20033/25/20033/25/2003PPASS
DetailsRon Ginner
###-#### OFFICE interceptor piping and vents installed to above ground. 3/25/2003 10:08:02 AM
Groundwork3/21/20033/24/20033/24/2003APASS
DetailsRon Ginner
oil interceptor tested to top of lid. small leak from seal of lid to tank. called walt bumgardner and he said it would be okay. each compartment of the tank must be vented with two inch back to bldg where these vents can be combined when above grade. vent from outlet of tank shall be extended by seperately through roof. 3/24/2003 3:35:38 PM
Plumbing Rough-in3/20/20033/21/20033/21/2003AFAIL
DetailsJim Johnson
grease trap ###-#### 3/21/2003 10:30:19 AM need to correct inlet and outlet elevation on interceptor and retest tank 3/21/2003 10:47:16 AM
Plumbing Rough-in3/19/20033/20/20033/20/2003PPASS
DetailsJim Johnson
###-#### underground inspection
Water and/or Sewer3/18/20033/19/20033/19/2003APART
DetailsJim Johnson
###-#### water line only test ok ok to cover 3/19/2003 12:20:59 PM