Final | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | PASS |
Jim Johnson
|
|
|
maryann; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Final | 4/6/2004 | 4/7/2004 | 4/7/2004 | A | PART |
Jim Johnson
|
|
|
marianna ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need to turn t&p drain line down on outside of building and caulk all fixtures at wall and floor home owner to recall when ready 4/7/2004 10:43:48 AM
|
Plumbing Rough-in | 10/24/2003 | 10/27/2003 | 10/27/2003 | A | PASS |
Jim Johnson
|
|
|
###-#### maria
|
Plumbing Rough-in | 10/22/2003 | 10/23/2003 | 10/23/2003 | A | PART |
Jim Johnson
|
|
|
###-#### maria need to move washer water and drain out of out side wall repipe venting for up stream water closet and shower increase 3/4 water line to 1 inch up to water heater provide cleanout,s for laundry tray and water closet support abs pipe every 4 feet support copper water piping every 6 feet talked to home owner on job site will recall when ready for reinspection 10/23/2003 12:15:48 PM
|
Water and/or Sewer | 8/29/2003 | 8/29/2003 | 8/29/2003 | P | PART |
Lee Rice
|
|
|
mariana- ###-####- re-insp water line changed to 1inch ok. 8/29/2003 11:53:09 AM
|
Water and/or Sewer | 8/29/2003 | 8/29/2003 | 8/29/2003 | P | PART |
Lee Rice
|
|
|
mariana- ###-####- re-insp water line changed to 1inch ok. 8/29/2003 11:53:09 AM
|
Water and/or Sewer | 8/28/2003 | 8/28/2003 | 8/28/2003 | P | FAIL |
Jim Johnson
|
|
|
water line ###-####--mariana need to increase water line to 1 inch 8/28/2003 4:35:29 PM
|