Sprinkler (Final) | 8/2/2004 | 8/3/2004 | 8/3/2004 | A | PASS |
Bill VanDegrift
|
|
|
###-#### eric final ok 8/3/2004 8:51:33 AM
|
Sprinkler (Final) | 7/30/2004 | 7/30/2004 | 7/30/2004 | P | FAIL |
Bill VanDegrift
|
|
|
###-#### Erick blowout tee prohibited upstream of dcva, 160 psi min poly required upstream of dcva, use approved worm drive clamps upstream of dcva, test dcva. 7/30/2004 2:31:23 PM
|