Final | 4/13/2005 | 4/13/2005 | 4/13/2005 | A | PASS |
Jim Johnson
|
|
|
|
Final | 4/11/2005 | 4/11/2005 | 4/11/2005 | P | PART |
Jim Johnson
|
|
|
leo; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie need anchor softner drain at washer box with 1 inch air gap both unit,s and provide flush plug on sewer cleanout in garage in unit 8517 4/11/2005 4:46:43 PM
|
Plumbing Rough-in | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | PASS |
Jim Johnson
|
|
|
leo; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Plumbing Rough-in | 1/28/2005 | 1/28/2005 | 1/28/2005 | P | FAIL |
Jim Johnson
|
|
|
leo ###-#### in unit 8513- need to remove fernco coupling from 3 inch pipe in over head and replace with approved coupling 2- need to roll island sink vent connection to drain line above center line and support island sink vent in floor joist every 4 feet also need a few more hanger,s on drain lines in crawl in unit 8517 need to move water piping 12 inches away from can lighting in overhead in kitchen area and test failed on DWV . left notice and called contractor will recall when ready 1/28/2005 2:41:58 PM
|