Final | 7/17/2006 | 7/17/2006 | 7/17/2006 | P | PASS |
Eric Strole
|
|
|
Scheduled by a contractor via Hello! on 7/17/2006 at 7:52:33 AM. Contact: ###-####.
|
Plumbing Rough-in | 4/21/2006 | 4/21/2006 | 4/21/2006 | P | PASS |
Daryl Spivey
|
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Plumbing Rough-in | 4/20/2006 | 4/20/2006 | 4/20/2006 | P | FAIL |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need to correct reverse grade in two inch drain line from 3x2 y to two inch y going to master tub and shower 2- need to correct leak,s in master bath tub shoe and on 3 inch st. 90 by cleanout under main bath in crawl and retest DWV system 3- need to move master bath tub and shower vent 10 feet away or 3 foot above upstair,s opening window on north side contractor to recall when ready
|
Plumbing Rough-in | 4/17/2006 | 4/18/2006 | 4/18/2006 | A | FAIL |
Daryl Spivey
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong no test on w/v, missing nail plates, water lines and waste in crawl needs strapped at appropriate lengths, and hose bibs need secured in walls above floor. ds
|