DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/7/20075/7/20075/7/2007APASS
DetailsEric Strole
Final5/7/20075/7/20075/7/2007PCANC
DetailsDaryl Spivey
dave - norco certificate ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
Final5/1/20075/3/20075/4/2007PPART
DetailsBill VanDegrift
josh; Phone #: ###-#### Internet Inspection Request from: Victoria Beall provide avb downstrean of solinoid valve. provide med gas certification. temp occ ok.
Final5/1/20075/1/20075/1/2007PCANC
DetailsBill VanDegrift
joshua ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Victoria Beall
Med/Gas Systems4/24/20074/25/20074/25/2007APASS
DetailsBill VanDegrift
med gas and ri ok
Med/Gas Systems4/24/20074/24/20074/24/2007APART
DetailsBill VanDegrift
start 24 hour test on the compressed air system 149 psi, marked with blue pen.
Med/Gas Systems4/23/20074/23/20074/23/2007PFAIL
DetailsEric Strole
Call Kirk and he will meet you on the site. Phone #: ###-#### Internet Inspection Request from: Kirk Johns-med air test failed.
Med/Gas Systems4/20/20074/23/20074/23/2007APART
DetailsEric Strole
med air failed, vac pass, plumber will call when ready for retest on med air. DO NOT COVER.
Med/Gas Systems4/19/20074/20/20074/20/2007APART
DetailsEric Strole
this was the start of 24 hr test on air & vac system.
Med/Gas Systems4/19/20074/19/20074/19/2007PFAIL
DetailsEric Strole
Pressure witness test. Phone #: ###-#### Internet Inspection Request from: Kirk Johns-need to support air line every 6'- need to support vac line every 4'- vac line needs graded 1/4" every 10'- need 150 psi on air & 15 psi on vac for 24 hr test- need stamped drawing for vac & air before final.
Plumbing Rough-in3/21/20073/21/20073/21/2007PPART
DetailsEric Strole
dwv & water pass, ok to cover walls that will not effect vac & air line system that still need installed & tested.
Plumbing Rough-in3/21/20073/22/20073/21/2007ACANC
DetailsEric Strole
kirk; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
Plumbing Rough-in3/20/20073/21/20073/21/2007PCANC
DetailsEric Strole
Scheduled by a contractor via Hello! on 3/20/2007 at 3:37:22 PM.
Plumbing Rough-in3/13/20073/13/20073/13/2007PPART
DetailsEric Strole
Kirk; Phone #: ###-#### Internet Inspection Request from: Stacie Backus-dwv & water pass, still need air & vac line's tested & sleeved.