Final | 10/15/2007 | 10/16/2007 | 10/16/2007 | A | PASS |
Eric Strole
|
|
|
|
Final | 9/14/2007 | 9/14/2007 | 9/14/2007 | P | PART |
Eric Strole
|
|
|
JOB CONTACT IS CHRIS BUSS Phone #: ###-#### Internet Inspection Request from: ADAM WARR-buss final pass, still need letter from boise school district.
|
Final | 8/22/2007 | 8/23/2007 | 8/23/2007 | P | CANC |
Eric Strole
|
|
|
JOB CONTACT IS CHRIS BUSS Phone #: ###-#### Internet Inspection Request from: KYLIE HICKS Inspection cancelled from web by: JENN STALEY
|
Final | 8/15/2007 | 8/16/2007 | 8/16/2007 | A | PART |
Eric Strole
|
|
|
JOB CONTACT IS CHRIS BUSS Phone #: ###-#### Internet Inspection Request from: KYLIE HICKS-temp ok, waiting to here from school district.
|
Other | 8/16/2007 | 8/16/2007 | 8/16/2007 | P | PASS |
Bill VanDegrift
|
|
|
|
Final | 8/14/2007 | 8/15/2007 | 8/15/2007 | A | FAIL |
Eric Strole
|
|
|
JOB CONTACT IS CHRIS BUSS Phone #: ###-#### Internet Inspection Request from: ADAM WARR-no final till last correction notice is addressed.need to change out pvc female adapters on drains under lab sinks to approved material, need spec sheet on traps for lab sinks, need to support traps.
|
Plumbing Rough-in | 7/17/2007 | 7/18/2007 | 7/18/2007 | A | PASS |
Eric Strole
|
|
|
CONTACT: CHRIS BUSS Phone #: ###-#### Internet Inspection Request from: JENN STALEY-this was the water tie in in mech room, rpba's need tested & certified & labeled & label all non potable water. need to add unions on rpba's, will check on final.
|
Plumbing Rough-in | 7/12/2007 | 7/12/2007 | 7/12/2007 | A | PASS |
Eric Strole
|
|
|
r/i pass, mech room still needs finished.
|
Other | 7/11/2007 | 7/12/2007 | 7/12/2007 | A | DONE |
Eric Strole
|
|
|
this was a conferance with bill wittkopf with boise schools & bill thomson, upgrades on backflow protection is being started in schools.
|
Other | 6/26/2007 | 6/27/2007 | 6/27/2007 | A | PART |
Eric Strole
|
|
|
add to first inspection note-need to isolate lab sinks in rooms 104,110,109,350,213,106,208,212 & 300 with rpba's-eye wash in kitchen needs spill proof vacuum breaker,eye wash in all janitor rooms need pvb's,kitchen area in room s11 needs rpba on water cooled condensers.
|
Other | 6/26/2007 | 6/26/2007 | 6/26/2007 | P | DONE |
Eric Strole
|
|
|
this was a conferance with thomson & criss wiyh buss on upgrades of school.need dbcv on service-need to isolate boiler equipment with a rpba-need to isolate ejector primer with a rpba-need hvb's on mop sink in boiler room-need rpba's on all soap dispensers in mop sink rooms.
|
Plumbing Rough-in | 6/25/2007 | 6/26/2007 | 6/26/2007 | A | PART |
Eric Strole
|
|
|
JOB CONTACT IS CHRIS BUSS, ASKED FOR INSPECTION AS EARLY IN MORNING AS POSSIBLE Phone #: ###-#### Internet Inspection Request from: KYLIE HICKS-water & dwv for wall inspection 0n sinks only pass.
|