PLM-Aging Inspection | 10/24/2007 | 10/24/2007 | 10/24/2007 | | PASS |
Eric Strole
|
|
|
|
DOC - Permit Finaled | 10/24/2007 | 10/24/2007 | 10/24/2007 | P | PASS |
Eric Strole
|
|
|
|
Other | 8/23/2007 | 8/24/2007 | 8/24/2007 | A | PART |
Eric Strole
|
|
|
this was a walk thru with bill thomson with united water. dishwasher in kitchen needs isolated with a rpba, janitors sinks need a pvb installed on eyewash & soap dispensers need rpba's, rpba for fire system in mech room & rpba in boiler room need to be moved to within 5' off flr, need hbv on boiler bib in mech room on janitors sink, all backflow devices need tested & certified.
|
Other | 8/23/2007 | 8/23/2007 | 8/23/2007 | P | CANC |
Eric Strole
|
|
|
|
Final | 8/21/2007 | 8/21/2007 | 8/21/2007 | P | PART |
Eric Strole
|
|
|
PLEASE USE JEFF S. AS THE CONTACT. THANK YOU. Phone #: ###-#### Internet Inspection Request from: JENN STALEY-temp final ok, still need signed letter from school district for upgrades required from water perveyer & upc.
|
Final | 8/16/2007 | 8/16/2007 | 8/16/2007 | P | PART |
Eric Strole
|
|
|
need tempered water to public lavs of 120 degree or less. temp ok.
|
Plumbing Rough-in | 7/18/2007 | 7/19/2007 | 7/19/2007 | A | PASS |
Eric Strole
|
|
|
JOB CONTACT IS SHAWN. Phone #: ###-#### Internet Inspection Request from: KYLIE HICKS
|
Plumbing Rough-in | 7/16/2007 | 7/17/2007 | 7/17/2007 | A | PART |
Eric Strole
|
|
|
THIS IS A PARTIAL ROUGH-IN AND THE CONTACT IS SHAWN R. Phone #: ###-#### Internet Inspection Request from: JENN STALEY-north end girls & boys bathrooms pass.
|
Other | 7/6/2007 | 7/9/2007 | 7/9/2007 | A | CANC |
Eric Strole
|
|
|
|
Other | 7/5/2007 | 7/6/2007 | 7/6/2007 | A | DONE |
Eric Strole
|
|
|
Mike Webb is contact. Would like a courtesy meeting to discuss some issues he sees before any work commences. Thank you. Phone #: ###-#### Internet Inspection Request from: Mike Davisson-this was a conferance on the school remodel.
|