Final | 8/19/2008 | 8/19/2008 | 8/21/2008 | P | PASS |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Final | 8/1/2008 | 8/4/2008 | 8/4/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 2 rooms in area A complete.and 1 sink.........ds
|
Plumbing Rough-in | 7/10/2008 | 7/11/2008 | 7/11/2008 | A | PASS |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy finished with area A waste, vent and water.........ds
|
Med/Gas Systems | 7/3/2008 | 7/7/2008 | 7/7/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Med gas rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test on wall good to cover.........ds
|
Med/Gas Systems | 7/3/2008 | 7/3/2008 | 7/3/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Med gas rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Jane Amy 150# test on boxes and lines in wall...1 room....ds
|
Plumbing Rough-in | 6/19/2008 | 6/20/2008 | 6/20/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 1 sink.. 3rd floor area A...ds
|
Plumbing Rough-in | 6/18/2008 | 6/19/2008 | 6/19/2008 | P | CANC |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy Inspection cancelled from web by: Jane Amy
|
Plumbing Rough-in | 6/18/2008 | 6/19/2008 | 6/18/2008 | A | CANC |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy Inspection cancelled from web by: Jane Amy
|
Final | 6/2/2008 | 6/2/2008 | 6/2/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy area B, C, D, E and part of area A ok for occupancy.....ds
|
Plumbing Rough-in | 4/11/2008 | 4/14/2008 | 4/14/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Rob @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy for sink area that was not done before.......ds
|
Plumbing Rough-in | 2/28/2008 | 2/29/2008 | 2/29/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-#### or Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 50 lb test omplete on area B mains...ds
|
Med/Gas Systems | 2/28/2008 | 2/28/2008 | 2/28/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy Areas B & C 150 lb. test passed....start 50 lb. 24 hr test.....ds
|
Med/Gas Systems | 2/4/2008 | 2/5/2008 | 2/5/2008 | A | PART |
Daryl Spivey
|
|
|
On Site contact is Rob @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy med gas test area A 24 hr test ok........ds
|
Plumbing Rough-in | 2/1/2008 | 2/4/2008 | 2/4/2008 | A | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS ROB @ ###-####. HE WILL ALSO NEED A MED-GAS INSPECTION. Phone #: ###-#### Internet Inspection Request from: Jane Amy partial R/I for area A for water, waste & vent and med gas stub outs of wall was initial test at 150 #..............ds
|
Med/Gas Systems | 1/18/2008 | 1/18/2008 | 1/18/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Rob @ ###-#### or Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr 50lb test for C, D, and E area ok......ds
|
Med/Gas Systems | 1/16/2008 | 1/17/2008 | 1/17/2008 | A | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS ROB @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy high pressure test ok.......start 24 hr test at 50 lbs. for main lines in areas C D& E.........ds
|
Plumbing Rough-in | 1/4/2008 | 1/7/2008 | 1/7/2008 | P | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS CORRY @ ###-####. HE WILL ALSO NEED MED-GAS INSPECTED. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test on med ga ok.......r/i area B ok.....ds
|
Med/Gas Systems | 1/4/2008 | 1/4/2008 | 1/4/2008 | P | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS CORRY @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 2x press. test good ......start 24 hr. test.........area B............ds
|
Med/Gas Systems | 12/7/2007 | 12/10/2007 | 12/10/2007 | A | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS CORRY @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test ok... good to cover walls on med gas stub outs area e....ds
|
Med/Gas Systems | 12/6/2007 | 12/7/2007 | 12/7/2007 | A | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS CORRY @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy area e ..150 test ok...start 50 lb 24 hr test...ds
|
Med/Gas Systems | 12/5/2007 | 12/6/2007 | 12/6/2007 | P | PART |
Daryl Spivey
|
|
|
On Site Contact is Corry @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy area b 150 lb. test just for main isolation valves....ds
|
Plumbing Rough-in | 12/4/2007 | 12/4/2007 | 12/4/2007 | P | PART |
Daryl Spivey
|
|
|
ON SITE CONTACT IS CORRY @###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy sec d and some of e...ds
|
Plumbing Rough-in | 11/14/2007 | 11/14/2007 | 11/14/2007 | P | CANC |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Med/Gas Systems | 11/14/2007 | 11/14/2007 | 11/14/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr. test on area D is ok and can cover walls....ds
|
Plumbing Rough-in | 11/12/2007 | 11/13/2007 | 11/13/2007 | A | CANC |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Med/Gas Systems | 11/13/2007 | 11/13/2007 | 11/13/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy initial 150 test for section D..start 50 lb. 24 hr. test...ds
|
Plumbing Rough-in | 11/8/2007 | 11/9/2007 | 11/9/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Plumbing Rough-in | 10/17/2007 | 10/17/2007 | 10/17/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Job#07-03 Phone #: ###-#### Internet Inspection Request from: SUE OGLESBY
|
Plumbing Rough-in | 10/16/2007 | 10/16/2007 | 10/16/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Plumbing Rough-in | 10/12/2007 | 10/15/2007 | 10/15/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. 3 East Tower Annex. Job# 07-03. Phone #: ###-#### Internet Inspection Request from: SUE OGLESBY
|
Plumbing Rough-in | 10/12/2007 | 10/12/2007 | 10/12/2007 | P | CANC |
Daryl Spivey
|
|
|
ALSO NEED MED GAS ROUGH IN. On site contact Corry @ ###-####. 3 East Tower Annex. Job# 07-03. Phone #: ###-#### Internet Inspection Request from: SUE OGLESBY
|
Med/Gas Systems | 10/11/2007 | 10/11/2007 | 10/11/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy area c .....start 24 hr. test on gas for wall outlets only.....ds
|
Plumbing Rough-in | 10/2/2007 | 10/2/2007 | 10/2/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Cable ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy ambulance parking ceiling area good to cover.....ds
|