Final | 5/14/2009 | 5/15/2009 | 5/15/2009 | A | PASS |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Plumbing Rough-in | 4/15/2009 | 4/15/2009 | 4/15/2009 | P | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Med/Gas Systems | 4/3/2009 | 4/6/2009 | 4/6/2009 | A | PART |
Daryl Spivey
|
|
|
Follow up inspection for Med Gas rough-in. On site contact is Padraic @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test complete...good to cover........ds
|
Med/Gas Systems | 4/3/2009 | 4/3/2009 | 4/3/2009 | P | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 150 lb test ok....start 24 hr test.........ds
|
Med/Gas Systems | 3/10/2009 | 3/11/2009 | 3/11/2009 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 test ok..good to cover.....ds
|
Med/Gas Systems | 3/9/2009 | 3/10/2009 | 3/10/2009 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Needs Med-Gas rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Jane Amy start 24 hr test........ds
|
Med/Gas Systems | 2/17/2009 | 2/18/2009 | 2/18/2009 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Need Med-Gas rough-in inspection. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test on wall good..............ds
|
Med/Gas Systems | 2/13/2009 | 2/17/2009 | 2/17/2009 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy initial 150# test ok.ds
|
Med/Gas Systems | 1/15/2009 | 1/16/2009 | 1/16/2009 | A | PART |
Daryl Spivey
|
|
|
skip............24 hr test ok...........ds
|
Med/Gas Systems | 1/14/2009 | 1/15/2009 | 1/15/2009 | P | PART |
Daryl Spivey
|
|
|
Med-gas rough-in inspection. On site contact is Corry. Phone #: ###-#### Internet Inspection Request from: Jane Amy pressure test ok.........2 rooms post op.....start 24 hr. test.............ds
|
Final | 1/5/2009 | 1/6/2009 | 1/6/2009 | A | PART |
Daryl Spivey
|
|
|
Partial final inspection. On site contact is Padraic @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy units 18-22 done........ds
|
Plumbing Rough-in | 12/9/2008 | 12/9/2008 | 12/9/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Mel Anderson @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 3 sinks in post op area B ok...............ds
|
Med/Gas Systems | 11/21/2008 | 11/24/2008 | 11/24/2008 | A | PART |
Daryl Spivey
|
|
|
24hr follow-up Plumbing/Med Gas Partial Inspection. On site contact is Padraic @ ###-#### or ###-####. Job#07-09 Phone #: ###-#### Internet Inspection Request from: SUE OGLESBY ok to cover..........ds
|
Med/Gas Systems | 11/20/2008 | 11/21/2008 | 11/21/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-####. Partial Med-Gas inspection needed. Phone #: ###-#### Internet Inspection Request from: Jane Amy start 24 hr test.......ds
|
Final | 10/27/2008 | 10/27/2008 | 10/27/2008 | A | PART |
Daryl Spivey
|
|
|
post op area done..........ds
|
Final | 10/24/2008 | 10/24/2008 | 10/24/2008 | P | CANC |
Daryl Spivey
|
|
|
On site contact is Corry @###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy cancelled by Skip via phone call........ds
|
Med/Gas Systems | 8/27/2008 | 8/29/2008 | 8/29/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test ok..............ds
|
Med/Gas Systems | 8/27/2008 | 8/28/2008 | 8/28/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 150 # test ok start 24 hr test............ds
|
Med/Gas Systems | 8/15/2008 | 8/18/2008 | 8/18/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test ok........ds
|
Med/Gas Systems | 8/15/2008 | 8/15/2008 | 8/15/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Padraic @ ###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy 150 # tst good.start 50 # 24 hr test..........ds
|
Med/Gas Systems | 8/6/2008 | 8/7/2008 | 8/7/2008 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr test ok...ds
|
Plumbing Rough-in | 8/6/2008 | 8/6/2008 | 8/6/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Will also need a partial med-gas inspection. Phone #: ###-#### Internet Inspection Request from: Jane Amy 150 lb intial test on 4 rooms for med gas....start 24 hr test..........waste and vent partial tests ok.........ds
|
Groundwork | 7/16/2008 | 7/17/2008 | 7/17/2008 | A | PASS |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
PLM-Aging Inspection | 7/4/2008 | 7/4/2008 | 7/7/2008 | | NR |
Daryl Spivey
|
|
|
wip
|
PLM-Aging Inspection | 4/28/2008 | 4/28/2008 | 4/29/2008 | | NR |
Daryl Spivey
|
|
|
wip
|
Plumbing Rough-in | 2/26/2008 | 2/26/2008 | 2/26/2008 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy equip. cleaning air line in pharmacy.....ok.ds
|
Water and/or Sewer | 2/14/2008 | 2/15/2008 | 2/15/2008 | A | CANC |
Daryl Spivey
|
|
|
|
Plumbing Rough-in | 2/15/2008 | 2/15/2008 | 2/15/2008 | A | PART |
Daryl Spivey
|
|
|
|
Plumbing Rough-in | 2/14/2008 | 2/14/2008 | 2/14/2008 | P | CANC |
Daryl Spivey
|
|
|
On site contact is Corry @###-#### Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Final | 12/18/2007 | 12/19/2007 | 12/19/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. This is a partial final inspection request. Phone #: ###-#### Internet Inspection Request from: Jane Amy all ok...need med gas paper work from Norco for final...sec. 5.............ds
|
Med/Gas Systems | 10/31/2007 | 11/1/2007 | 11/1/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 24 hr med gas test ok...ds
|
Med/Gas Systems | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy initial 150 lb test and start 24 hr test....ds
|
Plumbing Rough-in | 10/17/2007 | 10/17/2007 | 10/17/2007 | A | PART |
Daryl Spivey
|
|
|
MED GAS INSPECTION. On site contact is Corry @ ###-####. Job#07-09 Phone #: ###-#### Internet Inspection Request from: SUE OGLESBY 24 hr test on med gas stub outs passed ....ds
|
Med/Gas Systems | 10/16/2007 | 10/16/2007 | 10/16/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy 150 lb test and start 50 lb test...ds
|
Plumbing Rough-in | 10/8/2007 | 10/9/2007 | 10/9/2007 | A | PART |
Daryl Spivey
|
|
|
On site contact is Corry @ ###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy
|
Groundwork | 10/8/2007 | 10/8/2007 | 10/8/2007 | P | CANC |
Daryl Spivey
|
|
|
On site contact is Corry @ 86-5116. Phone #: ###-#### Internet Inspection Request from: Jane Amy Inspection cancelled from web by: Jane Amy
|
Plumbing Rough-in | 10/5/2007 | 10/5/2007 | 10/5/2007 | P | PART |
Daryl Spivey
|
|
|
On site contact is Corry @###-####. Phone #: ###-#### Internet Inspection Request from: Jane Amy med gas ...start 24 hr test...ds
|