Final | 1/22/2009 | 1/23/2009 | 1/23/2009 | A | PASS |
Jim Johnson
|
|
|
JOB CONTACT IS THAYNE Phone #: ###-#### Internet Inspection Request from: ADAM WARR
|
Final | 12/30/2008 | 12/31/2008 | 12/31/2008 | A | PART |
Eric Strole
|
|
|
JOB CONTACT IS THAYNE ###-#### Phone #: ###-#### Internet Inspection Request from: MARGGIE BUSS-irrigation is on a duel system-need to install a rpba on city water for lawn sprinklers.
|
Final | 12/22/2008 | 12/22/2008 | 12/22/2008 | P | PART |
Jim Johnson
|
|
|
JOB CONTACT IS THAYNE HILL Phone #: ###-#### Internet Inspection Request from: ADAM WARR need to provide approved backflow devices on hand held eye wash located by mop sink,s up and down staires or shorten hose to where eye wash will be above flood level rim of mop sink. need bee hive strainer on floor sink in up staires water heater room. as per nfpa99-c 2000 edition 5.3.3.5.7 & 5.3.3.5.7.1 need to provide an approved source of intake air for compressor ok temp
|
Final | 12/17/2008 | 12/18/2008 | 12/18/2008 | P | CANC |
Jim Johnson
|
|
|
CONTACT IS THAYNE ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS canc by contractor
|
Plumbing Rough-in | 10/20/2008 | 10/20/2008 | 10/20/2008 | P | PASS |
Jim Johnson
|
|
|
JOB CONTACT IS THAYNE HILL Phone #: ###-#### Internet Inspection Request from: ADAM WARR
|
Other | 10/16/2008 | 10/16/2008 | 10/16/2008 | A | PART |
Jim Johnson
|
|
|
conf. with plumber on backflow devices
|
Plumbing Rough-in | 10/8/2008 | 10/9/2008 | 10/9/2008 | P | PART |
Eric Strole
|
|
|
JOB CONTACT IS THAYNE HILL Phone #: ###-#### Internet Inspection Request from: ADAM WARR-dwv & water on 2nd flr except sience lab pass, sience lab is dwv stub up & overhead water.
|
Plumbing Rough-in | 8/25/2008 | 8/26/2008 | 8/26/2008 | A | PART |
Jim Johnson
|
|
|
PLEASE USE THAYNE AS CONTACT, THANK YOU. Phone #: ###-#### Internet Inspection Request from: JENN STALEY first floor and second floor under floor rough-in test ok
|
Plumbing Rough-in | 7/25/2008 | 7/28/2008 | 7/28/2008 | A | PART |
Jim Johnson
|
|
|
PLEASE USE THAYNE AS CONTACT, THANK YOU. Phone #: ###-#### Internet Inspection Request from: JENN STALEY portion of D W V test ok as noted on Buss plan,s in job trailer
|
Plumbing Rough-in | 6/23/2008 | 6/24/2008 | 6/24/2008 | A | PASS |
Jim Johnson
|
|
|
THIS IS AN UNDERGROUND INSPECTION. PLEASE USE THAYNE FOR CONTACT, THANK YOU. Phone #: ###-#### Internet Inspection Request from: JENN STALEY vac. and air lines test ok
|
Groundwork | 6/10/2008 | 6/11/2008 | 6/11/2008 | A | PART |
Jim Johnson
|
|
|
THIS WILL BE AN UNDERGROUND WATER INSPECTION. PLEASE USE THAYNE AS CONTACT, THANK YOU. Phone #: ###-#### Internet Inspection Request from: JENN STALEY watr stub out,s to building tst ok
|
Groundwork | 6/6/2008 | 6/9/2008 | 6/9/2008 | A | PASS |
Jim Johnson
|
|
|
PLEASE USE THAYNE AS CONTACT, THANK YOU. Phone #: ###-#### Internet Inspection Request from: JENN STALEY
|