Final | 10/26/2009 | 10/27/2009 | 10/27/2009 | A | PASS |
Bill VanDegrift
|
|
|
JOB CONTACT IS CHRIS BUSS Phone #: ###-#### Internet Inspection Request from: ADAM WARR
|
Final | 10/21/2009 | 10/22/2009 | 10/22/2009 | A | PART |
Bill VanDegrift
|
|
|
CONTACT IS CHRIS BUSS ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS hand sinks in the kitchen ok dental area not ready
|
Other | 8/26/2009 | 8/26/2009 | 8/26/2009 | P | DONE |
Eric Strole
|
|
|
faxed correction notice to buss.
|
Final | 8/25/2009 | 8/25/2009 | 8/26/2009 | P | PART |
Eric Strole
|
|
|
JOB CONTACT IS AB JENSEN Phone #: ###-#### Internet Inspection Request from: ADAM WARR-need tempered water of 120 degree water or less to hand sinks in kitchen.
|
Groundwork | 8/11/2009 | 8/12/2009 | 8/12/2009 | P | PASS |
Eric Strole
|
|
|
test on interceptor pass.
|
Groundwork | 8/11/2009 | 8/11/2009 | 8/11/2009 | P | PART |
Eric Strole
|
|
|
CONTACT IS AB ###-#### INSPECTION IS FOR GREASE INTERCEPTOR Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS-start of 24 hr test on interceptor.
|
Final | 8/6/2009 | 8/7/2009 | 8/7/2009 | A | PART |
Eric Strole
|
|
|
CONTACT IS AB ###-####. FINAL INSPECTION IS FOR A,C,&D WINGS. Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS-a-c-d wing pass. need to label all backflow devices, need vacuum breaker on hand held shower, set dishwasher in teachers lounge, finish dental & kitchen area. need test on grease interceptor. temp final ok.
|
Other | 8/6/2009 | 8/6/2009 | 8/6/2009 | P | PART |
Eric Strole
|
|
|
conferance for kitchen area on backflows required.
|
PLM-Aging Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 | | PASS |
Eric Strole
|
|
|
|
Plumbing Rough-in | 5/29/2009 | 5/29/2009 | 5/29/2009 | A | PASS |
Daryl Spivey
|
|
|
JOB CONTACT IS AB JENSEN Phone #: ###-#### Internet Inspection Request from: ADAM WARR Dental area tested ok.................ds
|
Plumbing Rough-in | 5/27/2009 | 5/28/2009 | 5/28/2009 | P | NR |
Daryl Spivey
|
|
|
CONTACT IS AB ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS
|
Plumbing Rough-in | 5/19/2009 | 5/20/2009 | 5/20/2009 | A | PART |
Bill VanDegrift
|
|
|
contact is Ab ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS water in the kitchen, restroom to the south ok.
|
Plumbing Rough-in | 4/29/2009 | 4/30/2009 | 4/30/2009 | A | PART |
Bill VanDegrift
|
|
|
Partial Rough-in inspection. Job Contact is AB ###-#### Phone #: ###-#### Internet Inspection Request from: MARGGIE BUSS roof drains and of east, south east and north ok
|
Plumbing Rough-in | 4/27/2009 | 4/28/2009 | 4/28/2009 | P | PART |
Bill VanDegrift
|
|
|
JOB CONTACT IS AB JENSEN Phone #: ###-#### Internet Inspection Request from: ADAM WARR KITCHEN DWV AND RD,OF TEST OK, DWV FOR 2 SINKS SOUTH OF THE KITCHEN
|
Plumbing Rough-in | 4/21/2009 | 4/22/2009 | 4/22/2009 | A | PART |
Bill VanDegrift
|
|
|
JOB CONTACT IS AB JENSEN Phone #: ###-#### Internet Inspection Request from: ADAM WARR special ed restroom and hand sink in next room north ok. roof drains need s.s. 1/4 bends in horizontal to horizontal and vertical to horizontal offsets.
|
Plumbing Rough-in | 4/6/2009 | 4/7/2009 | 4/7/2009 | P | PART |
Eric Strole
|
|
|
contact is Ab ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS-water in c-wing pass, bath group south side of c-wing dwv pass.
|
Plumbing Rough-in | 3/31/2009 | 4/1/2009 | 4/1/2009 | A | PART |
Bill VanDegrift
|
|
|
REQUEST IS FOR PARTIAL ROUGH IN INSPECTION. CONTACT IS AB ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS partial ri ok last of dwv and water in the A wing, dwv test in C wing, water mains through C wing and into dentist clinic, no fixture branches.
|
Plumbing Rough-in | 3/10/2009 | 3/10/2009 | 3/10/2009 | P | PART |
Bill VanDegrift
|
|
|
(D) north east wing ri ok
|
Plumbing Rough-in | 3/9/2009 | 3/10/2009 | 3/10/2009 | A | FAIL |
Bill VanDegrift
|
|
|
JOB CONTACT IS AB JENSEN Phone #: ###-#### Internet Inspection Request from: ADAM WARR change 1/4 bend to SS waste leak on wc face plates.
|
Plumbing Rough-in | 2/23/2009 | 2/24/2009 | 2/24/2009 | P | PART |
Eric Strole
|
|
|
INSPECTION IS FOR A PARTIAL ROUGH IN. CONTACT IS AB ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS-north side of a-wing up to fire wall on south side pass. (fix san tees on vents that are installed in the wrong direction)Dont need to retest.
|
PLM-Aging Inspection | 1/19/2009 | 1/19/2009 | 1/20/2009 | | PASS |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 11/19/2008 | 11/19/2008 | 11/19/2008 | A | NR |
Bill VanDegrift
|
|
|
stopped by to check the interceptor test but it wasn't ready
|
Groundwork | 10/28/2008 | 10/29/2008 | 10/29/2008 | P | PART |
Daryl Spivey
|
|
|
INSPECTION IS FOR PARTIAL UNDERGROUND-CONTACT IS AB ###-####. Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS area tested....is ok............ds
|
Groundwork | 10/27/2008 | 10/28/2008 | 10/28/2008 | A | PART |
Bill VanDegrift
|
|
|
JOB CONTACT IS AB JENSEN Phone #: ###-#### Internet Inspection Request from: ADAM WARR west end main and restroom group gw ok
|
Groundwork | 10/24/2008 | 10/24/2008 | 10/24/2008 | P | PART |
Daryl Spivey
|
|
|
south end area tested ok.......w/v.........ds
|
Groundwork | 10/23/2008 | 10/24/2008 | 10/24/2008 | A | NR |
Bill VanDegrift
|
|
|
GROUND WORK INSPECTION FOR SEWER. CONTACT IS JOSH-###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS still piping
|
Groundwork | 10/23/2008 | 10/23/2008 | 10/23/2008 | P | PART |
Bill VanDegrift
|
|
|
east side gw from south 2/3 rd of the way to north. not dental area.
|
Groundwork | 10/22/2008 | 10/23/2008 | 10/23/2008 | P | FAIL |
Bill VanDegrift
|
|
|
WOULD LIKE TO REQUEST A PARTIAL GROUND WORK INSPECTION ON THE SOUTH SIDE OF BUILDING. CONTACT IS HENRY ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS leaky
|
Water and/or Sewer | 10/22/2008 | 10/22/2008 | 10/22/2008 | P | FAIL |
Bill VanDegrift
|
|
|
hammond butterfly valves are not NSF approved for use in potable water service lines, remove valve from service line. UPC 605 requires the use of full port valver in water service piping.
|
Groundwork | 10/16/2008 | 10/17/2008 | 10/17/2008 | A | PART |
Bill VanDegrift
|
|
|
10:30 inspection for test. partial gw kitcken, ss trunk west side
|
Groundwork | 10/15/2008 | 10/16/2008 | 10/16/2008 | P | PART |
Eric Strole
|
|
|
INSPECTION IS FOR PARTIAL UNDERGROUND. CONTACT IS AB ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS-section complete is marked on plans in job trailer. ok to cover if need to as long as test is holding.
|
Groundwork | 10/15/2008 | 10/16/2008 | 10/15/2008 | A | CANC |
Bill VanDegrift
|
|
|
INSPECTION IS FOR PARTIAL UNDERGROUND. CONTACT IS AB ###-#### Phone #: ###-#### Internet Inspection Request from: LENNIE BUSS Inspection cancelled from web by: LENNIE BUSS
|