Final | 12/2/2009 | 12/2/2009 | 12/2/2009 | A | PASS |
Bill VanDegrift
|
|
|
|
PLM-Aging Inspection | 11/18/2009 | 11/18/2009 | 11/18/2009 | | PASS |
Bill VanDegrift
|
|
|
|
Final | 9/16/2009 | 9/17/2009 | 9/17/2009 | A | DONE |
Eric Strole
|
|
|
this was to drop off correction notice.
|
Water and/or Sewer | 9/9/2009 | 9/9/2009 | 9/9/2009 | P | FAIL |
Eric Strole
|
|
|
24 hr test on interceptor fail at truck wash.
|
Water and/or Sewer | 8/18/2009 | 8/19/2009 | 8/19/2009 | A | PART |
Eric Strole
|
|
|
8:30 am vac test.-test on all manholes pass, will final permit after all interceptors are tested.
|
Water and/or Sewer | 8/7/2009 | 8/12/2009 | 8/12/2009 | A | PART |
Eric Strole
|
|
|
8:30-vacuum test on manholes.-need to test 2 manholes on south side, all other manholes pass.
|
Other | 8/6/2009 | 8/6/2009 | 8/6/2009 | P | CANC |
Eric Strole
|
|
|
|
PLM-Aging Inspection | 6/22/2009 | 6/22/2009 | 6/22/2009 | | PASS |
Bill VanDegrift
|
|
|
|
Other | 4/22/2009 | 4/22/2009 | 4/22/2009 | P | PASS |
Bill VanDegrift
|
|
|
checked up on mh that seemed to show some water on camera. looked ok.
|
Water and/or Sewer | 3/3/2009 | 3/3/2009 | 3/3/2009 | A | PART |
Eric Strole
|
|
|
test between #4 & 5 manhole & south of #5 pass.
|
Water and/or Sewer | 2/24/2009 | 2/24/2009 | 2/24/2009 | A | PART |
Bill VanDegrift
|
|
|
sewer service to dispatch ok
|
Water and/or Sewer | 2/24/2009 | 2/24/2009 | 2/24/2009 | P | PART |
Bill VanDegrift
|
|
|
set mh at offset to interceptor at dispatch
|
Water and/or Sewer | 2/19/2009 | 2/19/2009 | 2/19/2009 | A | PART |
Bill VanDegrift
|
|
|
picked up sewer video
|
Water and/or Sewer | 2/18/2009 | 2/18/2009 | 2/18/2009 | A | PASS |
Bill VanDegrift
|
|
|
eastern most service to the building test ok
|
Water and/or Sewer | 2/17/2009 | 2/17/2009 | 2/17/2009 | P | PART |
Bill VanDegrift
|
|
|
east future service to the main building air test failed. 8" main test complete and good, west southern service good to the manhole with the east service tested ok the south service is incomplete, south east service main is good to the manhole and the south service branch for 50' tested ok, the east and west branches incomplete.
|
Water and/or Sewer | 2/13/2009 | 2/17/2009 | 2/17/2009 | A | PART |
Bill VanDegrift
|
|
|
Scheduled via mobile device. testing mains
|
Water and/or Sewer | 2/13/2009 | 2/16/2009 | 2/17/2009 | A | CANC |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 2/12/2009 | 2/13/2009 | 2/13/2009 | A | PART |
Bill VanDegrift
|
|
|
no piping today
|
Water and/or Sewer | 2/12/2009 | 2/12/2009 | 2/12/2009 | A | CANC |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 2/11/2009 | 2/12/2009 | 2/12/2009 | A | PART |
Bill VanDegrift
|
|
|
6" service heading to truck service area
|
Water and/or Sewer | 2/11/2009 | 2/11/2009 | 2/11/2009 | A | PART |
Bill VanDegrift
|
|
|
moving back to mh12
|
Water and/or Sewer | 2/10/2009 | 2/10/2009 | 2/10/2009 | A | PART |
Eric Strole
|
|
|
sewer & next manhole south of manhole #5 installed.
|
Water and/or Sewer | 2/10/2009 | 2/10/2009 | 2/10/2009 | A | PART |
Eric Strole
|
|
|
this inspection was done on 2-9-09, just starting digging for laterial off manhole #5 going south.
|
Water and/or Sewer | 2/4/2009 | 2/5/2009 | 2/5/2009 | A | PART |
Bill VanDegrift
|
|
|
10:00 am testing test three services ok
|
Water and/or Sewer | 2/3/2009 | 2/4/2009 | 2/4/2009 | A | PART |
Eric Strole
|
|
|
service to bldg off manhole 10, sewer up to & including manhole 11 complete, need service from 11 to bldg.
|
Water and/or Sewer | 2/3/2009 | 2/3/2009 | 2/3/2009 | P | PART |
Bill VanDegrift
|
|
|
up to mh10
|
Water and/or Sewer | 2/2/2009 | 2/3/2009 | 2/3/2009 | A | PART |
Bill VanDegrift
|
|
|
out of mh9 heading east
|
Water and/or Sewer | 2/2/2009 | 2/2/2009 | 2/2/2009 | P | PART |
Bill VanDegrift
|
|
|
up to mh9 and its service to bldg.
|
Water and/or Sewer | 1/30/2009 | 2/2/2009 | 2/2/2009 | A | PART |
Bill VanDegrift
|
|
|
heading east out of mh8
|
Water and/or Sewer | 1/29/2009 | 1/30/2009 | 1/30/2009 | A | PART |
Bill VanDegrift
|
|
|
1st 6" service to the building ok
|
Water and/or Sewer | 1/29/2009 | 1/29/2009 | 1/29/2009 | P | PART |
Bill VanDegrift
|
|
|
comb. waste and vent to equipment room will add relief vents at floor cleanouts on long main through building.
|
Water and/or Sewer | 1/28/2009 | 1/29/2009 | 1/29/2009 | A | PART |
Bill VanDegrift
|
|
|
good progress
|
Water and/or Sewer | 1/28/2009 | 1/28/2009 | 1/28/2009 | P | PASS |
Bill VanDegrift
|
|
|
will call starting up again
|
Water and/or Sewer | 12/24/2008 | 12/29/2008 | 12/29/2008 | A | NH |
Bill VanDegrift
|
|
|
not working
|
Water and/or Sewer | 12/22/2008 | 12/23/2008 | 12/24/2008 | A | NR |
Bill VanDegrift
|
|
|
not working today
|
Water and/or Sewer | 12/19/2008 | 12/22/2008 | 12/22/2008 | A | PART |
Bill VanDegrift
|
|
|
working on storm drains today
|
Water and/or Sewer | 12/18/2008 | 12/19/2008 | 12/19/2008 | A | PART |
Bill VanDegrift
|
|
|
pulled off sewer, back on storm drains.
|
Water and/or Sewer | 12/18/2008 | 12/18/2008 | 12/18/2008 | P | CANC |
Eric Strole
|
|
|
|
Water and/or Sewer | 12/17/2008 | 12/18/2008 | 12/18/2008 | A | PART |
Eric Strole
|
|
|
no activity on sewer at this time.
|
Water and/or Sewer | 12/17/2008 | 12/17/2008 | 12/17/2008 | P | CANC |
Eric Strole
|
|
|
sorry bill, to late burr
|
Water and/or Sewer | 12/16/2008 | 12/17/2008 | 12/17/2008 | A | PART |
Eric Strole
|
|
|
up to third manhole.
|
Water and/or Sewer | 12/15/2008 | 12/16/2008 | 12/16/2008 | A | PART |
Bill VanDegrift
|
|
|
another 150'
|
Water and/or Sewer | 12/12/2008 | 12/15/2008 | 12/15/2008 | A | PART |
Bill VanDegrift
|
|
|
another 120'
|
Water and/or Sewer | 12/11/2008 | 12/12/2008 | 12/12/2008 | A | PART |
Bill VanDegrift
|
|
|
Scheduled via mobile device. about 100' east of the second mh.
|
Water and/or Sewer | 12/11/2008 | 12/11/2008 | 12/12/2008 | P | PART |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 12/10/2008 | 12/11/2008 | 12/11/2008 | A | PART |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 12/10/2008 | 12/10/2008 | 12/10/2008 | P | PART |
Bill VanDegrift
|
|
|
+80'
|
Water and/or Sewer | 12/9/2008 | 12/10/2008 | 12/10/2008 | A | PART |
Bill VanDegrift
|
|
|
one stick starting at the west main sewer mh.
|
Water and/or Sewer | 12/9/2008 | 12/9/2008 | 12/9/2008 | P | PART |
Bill VanDegrift
|
|
|
starting on sewer again
|
Water and/or Sewer | 11/3/2008 | 11/4/2008 | 11/4/2008 | A | PART |
Bill VanDegrift
|
|
|
conference on storm drain inspections. just the line serving the interior roof drains is going to be inspected by pds.
|
Water and/or Sewer | 10/23/2008 | 10/31/2008 | 10/31/2008 | A | CANC |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 10/23/2008 | 10/30/2008 | 10/30/2008 | A | PART |
Bill VanDegrift
|
|
|
pulled off sewer and are working on the storm drain
|
Water and/or Sewer | 10/23/2008 | 10/29/2008 | 10/29/2008 | A | PART |
Bill VanDegrift
|
|
|
rocks
|
Water and/or Sewer | 10/23/2008 | 10/28/2008 | 10/28/2008 | A | PART |
Bill VanDegrift
|
|
|
offset to the north complete and set to run east.
|
Water and/or Sewer | 10/23/2008 | 10/27/2008 | 10/27/2008 | A | PART |
Bill VanDegrift
|
|
|
their at the offset at the top of the hill
|
Water and/or Sewer | 10/23/2008 | 10/24/2008 | 10/24/2008 | P | PART |
Jim Johnson
|
|
|
no activity on second manhole at base of hill at this time 10/24/08 3:15 pm
|
Water and/or Sewer | 10/23/2008 | 10/24/2008 | 10/24/2008 | A | PART |
Bill VanDegrift
|
|
|
piped over to the base of the hill ok
|
Water and/or Sewer | 10/23/2008 | 10/23/2008 | 10/23/2008 | P | PART |
Bill VanDegrift
|
|
|
troy Phone #: ###-#### 1st mh set ok
|
Water and/or Sewer | 10/23/2008 | 10/23/2008 | 10/23/2008 | A | PART |
Bill VanDegrift
|
|
|
just getting started on the sewer
|