Final | 5/21/2009 | 5/22/2009 | 5/22/2009 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Van Wey
|
Final | 5/12/2009 | 5/13/2009 | 5/13/2009 | A | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Van Wey still not tested
|
Final | 5/10/2009 | 5/11/2009 | 5/11/2009 | A | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Van Wey not tested
|
PLM-Aging Inspection | 5/5/2009 | 5/5/2009 | 5/5/2009 | | PASS |
Bill VanDegrift
|
|
|
no calls
|
Plumbing Rough-in | 3/5/2009 | 3/5/2009 | 3/5/2009 | P | PASS |
Daryl Spivey
|
|
|
Internet Inspection Request from: Brandon Van Wey
|
Groundwork | 3/3/2009 | 3/4/2009 | 3/3/2009 | A | PART |
Eric Strole
|
|
|
ground work pass. need to isolate dishwasher with a rpba, need to isolate ice tea maker with a dbca, need to isolate coffee & espresso with a rpba, need to isolate steamer with a rpba, need to isolate carbonaters with a rpba, need to isolate ice machine with a dbca or have a 1" airgap, need to isolate juicer with a dbca, need to isolate maximixer with a rpba, soap dispenser at mop sink needs it's own water supply & all hosebibs need hosebib vacuum breakers.
|