Permit Information
Permit NumberPLM09-00427
StatusFinaled
Name EXCEL PLUMBING
Site Address 12349 W MCMILLAN
Project NameScott Wright Dental Office
Customer Number 
ePlanReview 
Description
Install 3 waterclosets, 13 sinks, 1 WaterHeater per initial cert of value $28,000///3-30-09 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/5/20098/6/20098/6/2009APASS
DetailsJim Johnson
Phone #: ###-#### Internet Inspection Request from: bob pond
Final7/31/20098/3/20098/3/2009ANR
DetailsJim Johnson
Bob Phone #: ###-####
Final7/29/20097/30/20097/30/2009APART
DetailsJim Johnson
Please call at least 30 mins prior to inspection-Bob Phone #: ###-#### need 120 dgree hot water limitation to lav need hose bib vaccume breaker on all boiler drain,s provide idenification card,s on all back flow devices need med gas certification oked temp no sign off card on site
PLM-Aging Inspection7/6/20097/6/20097/6/2009 PASS
DetailsJim Johnson
Plumbing Rough-in5/6/20095/6/20095/6/2009PPART
DetailsJim Johnson
Bob- also med gas Phone #: ###-#### water test ok
Med/Gas Systems5/5/20095/6/20095/6/2009PPART
DetailsJim Johnson
24 hour test on med / gas test ok
Med/Gas Systems5/5/20095/5/20095/5/2009PPART
DetailsEric Strole
start 24 hr test on med system.
Groundwork5/5/20095/5/20095/5/2009PPASS
DetailsEric Strole
Bob Phone #: ###-####
Plumbing Rough-in4/30/20095/1/20095/1/2009APART
DetailsEric Strole
vent has been corrected, part of ground work in baths are to be replumbed. need to call for inspection when complete.
Plumbing Rough-in4/30/20094/30/20094/30/2009PCANC
DetailsEric Strole
Plumbing Rough-in4/29/20094/30/20094/30/2009APART
DetailsEric Strole
Bob Phone #: ###-####-over 40 ' on 2" horizontal vent, dwv test pass.
Water and/or Sewer4/6/20094/6/20094/6/2009AFAIL
DetailsEric Strole
Scheduled by a contractor via Hello! on 4/6/2009 at 6:21:17 AM. Contact: ###-####.water service needs to be of approved materials per 2003 upc.
Med/Gas Systems4/2/20094/2/20094/2/2009PPART
DetailsEric Strole
in slab vacuum pass
Med/Gas Systems4/1/20094/2/20094/2/2009APART
DetailsEric Strole
Med/Gas Systems4/1/20094/1/20094/1/2009PPART
DetailsEric Strole
start 24hr test at 5 psi on vacuum in slab.
Groundwork4/1/20094/1/20094/1/2009PPART
DetailsEric Strole
dwv for ground work pass.
Groundwork4/1/20094/1/20094/1/2009APART
DetailsEric Strole
Eric, we are looking at late morning groundwork inspection...say 11am-noon...thanks Bob. Phone #: ###-#### Internet Inspection Request from: bob pond-dwv test failed, ok to cover as long as test is good on reinspection.
Other3/30/20093/31/20093/31/2009APART
DetailsEric Strole
conferance on air & vac system-there is a tennis ball stuck in the 2" pvc building water supply, after line is dug up & repaired we need a water sample tested for contamination due to a sewer camera was used to locate tennis ball.
Plumbing Rough-in3/30/20093/30/20093/30/2009PPART
DetailsEric Strole
Bob Phone #: 230-0-trunk line ok to cover, still need all branch drains.