Final | 6/2/2009 | 6/2/2009 | 6/2/2009 | A | PASS |
Bill VanDegrift
|
|
|
ok from legal for easement final ok
|
Other | 4/29/2009 | 4/29/2009 | 4/29/2009 | A | PASS |
Bill VanDegrift
|
|
|
stopped by , talked to owner about not paving untill sewer easement issues are taken care of.
|
Water and/or Sewer | 4/13/2009 | 4/13/2009 | 4/13/2009 | P | FAIL |
Bill VanDegrift
|
|
|
dropped off correction notice about the sewer easement. the sanitary sewer service for this project crosses another property prior to connection to the public sewer system. provide a utility maintenance agreement for this purpose, recorded with the county prior to any further work on this sewer project. this notice follows conversations and submittal of an existing access easement agreement for review, from owner.
|
Water and/or Sewer | 4/10/2009 | 4/13/2009 | 4/13/2009 | A | FAIL |
Eric Strole
|
|
|
water line pass, grade on sewer is good.do not cover sewer till sewer easement issues are resolved.
|
Water and/or Sewer | 4/9/2009 | 4/10/2009 | 4/10/2009 | P | PASS |
Eric Strole
|
|
|
test on interceptor pass.
|
Water and/or Sewer | 4/9/2009 | 4/9/2009 | 4/9/2009 | P | FAIL |
Eric Strole
|
|
|
start 24 hr test on interceptor, do not cover sewer till easement issues are resolved.
|
Water and/or Sewer | 4/8/2009 | 4/9/2009 | 4/9/2009 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-####-need to find out about easement & if sewer thru easement is ok. need to grade sewer so not to be flat, need test port & c/o for grease interceptor. need to change out sch 80 female adaptor on water service to approved fitting.
|