Permit Information
Permit NumberPLM10-02393
StatusFinaled
Name PAIGE MECHANICAL GROUP INC
Site Address 4274 N EAGLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Plumbing Permit - New: all plumnbing
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/24/20115/25/20115/25/2011APASS
DetailsJim Johnson
Please call Dave with CM at ###-#### 1/2 hr before you arrive so he can unlock the building. Any questions with the inspection itself should be referred to Darren Paige at ###-#### Phone #: ###-#### >> Inspection requested via web by Nicholas Paige
Final5/23/20115/23/20115/24/2011PPART
DetailsJim Johnson
Please call Dave with CM co 1/2 before you arrive so he can unlock the building. Any questions with the inspection itself should be referred to Darren Paige at ###-#### Phone #: ###-#### >> Inspection requested via web by Nicholas Paige need to provide identification lables on all backflow devices and signage on model trimer water outlet. need to complete all water connection to all island sink ,s called contractor will recall when ready oked temp
PLM-Aging Inspection4/18/20114/18/20114/18/2011 PASS
DetailsJim Johnson
Med/Gas Systems2/15/20112/15/20112/15/2011PCANC
DetailsJim Johnson
Please call Bill with any questions
Phone #: ###-#### >> Inspection requested via web by Nicholas Paige canc contractor called in wrong address and permit number
Med/Gas Systems1/21/20111/24/20111/24/2011APASS
DetailsJim Johnson
med gas pressure test -test ok
Med/Gas Systems1/20/20111/21/20111/21/2011PPART
DetailsJim Johnson
Please call Darren with any Questions Phone #: ###-#### >> Inspection requested via web by Nicholas Paige start of 24 hr. pressure test
Med/Gas Systems1/14/20111/18/20111/18/2011AFAIL
DetailsJim Johnson
inspect med gas....call Bill at ###-#### or Darren at ###-#### Phone #: ###-#### >> Inspection requested via web by joe paige as per NFPA 99C 5.3.12.2.3.5 need to test gas piping system at 1.5 times system working pressure but not less than a gage pressure of 150 psi. called Darren will retest will recall when ready
Plumbing Rough-in12/16/201012/17/201012/17/2010APASS
DetailsJim Johnson
call Darren with any questions Phone #: ###-#### >> Inspection requested via web by Nicholas Paige
Plumbing Rough-in12/15/201012/16/201012/16/2010AFAIL
DetailsJim Johnson
call Doran please Phone #: ###-#### >> Inspection requested via web by joe paige test failed on D W V test failed on water need to pipe side by side sink,s with approved cross . need to provide nail plates where needed contractor to recall when ready
Groundwork11/8/201011/8/201011/8/2010PPASS
DetailsJim Johnson
call Darren please Phone #: ###-#### >> Inspection requested via web by joe paige water and sewer lines outside foundation ok ok to cover