Permit Information
Permit NumberPLM11-00805
StatusFinaled
Name BUSS MECHANICAL SERVICES INC
Site Address 506 N LATAH ST
Project NameBOISE CAT CLINIC
Customer Number 
ePlanReviewNo
Description
Plumbing Permit - Alteration: PLUMBING WASTE & VENTS,FIXTURES
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/9/20118/10/20118/10/2011PPASS
DetailsBill VanDegrift
JOB CONTACT IS JAY. PLEASE CALL FIRST FOR ACCESS TO BUILDING Phone #: ###-#### >> Inspection requested via web by ADAM WARR
Final8/5/20118/5/20118/5/2011PPART
DetailsEric Strole
JOB CONTACT IS NATE Phone #: ###-#### >> Inspection requested via web by ADAM WARR-spray hoses on faucets need to retract on there own.
Final7/11/20117/11/20117/11/2011PPART
DetailsEric Strole
JOB CONTACT IS NATE ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS-partial final, ok to move equipment in only.
Plumbing Rough-in5/12/20115/13/20115/13/2011APART
DetailsDaryl Spivey
Waste and vent tested ok.........ds
Plumbing Rough-in5/12/20115/12/20115/12/2011PPART
DetailsBill VanDegrift
water test on
Plumbing Rough-in5/10/20115/11/20115/11/2011APART
DetailsBill VanDegrift
JOB CONTACT IS NATE ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS conference,, basement drainage for equipment must be piped to indirect waste receptor with sealed and vented sump. remove R.P. in the crawl space. floor sinks under treatment sinks must not be enclosed in cabinets. DCVA required on sprinkler in bottle storage room.