Final | 12/13/2011 | 12/14/2011 | 12/14/2011 | A | PASS |
Eric Strole
|
|
|
|
Final | 12/12/2011 | 12/13/2011 | 12/13/2011 | P | FAIL |
Eric Strole
|
|
|
need hole at 90 on T&P's, need to verify glue used on cpvc and main shutoff valves need to be accessible.
|
Other | 12/8/2011 | 12/9/2011 | 12/9/2011 | A | CANC |
Eric Strole
|
|
|
JOB # 15945. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Other | 12/7/2011 | 12/8/2011 | 12/7/2011 | A | DONE |
Eric Strole
|
|
|
JOB # 15945 - CALL BRIAN @ ###-####. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes-This was a conferance on T&P termination.(T&P needs to run to an approved location.)
|
Plumbing Rough-in | 9/8/2011 | 9/9/2011 | 9/9/2011 | A | PASS |
Eric Strole
|
|
|
JOB # 15945. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Groundwork | 7/13/2011 | 7/14/2011 | 7/14/2011 | A | PASS |
Eric Strole
|
|
|
JOB # 15945. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Water and/or Sewer | 7/1/2011 | 7/5/2011 | 7/5/2011 | A | PASS |
Eric Strole
|
|
|
JOB # 15945. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Water and/or Sewer | 7/1/2011 | 7/1/2011 | 7/1/2011 | P | PASS |
Eric Strole
|
|
|
|
Water and/or Sewer | 6/30/2011 | 7/1/2011 | 7/1/2011 | A | PART |
Eric Strole
|
|
|
15945 - Please schedule for after 9 a.m. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes-sewer pass, need to run extra waterline for premis protection
|