Final | 1/24/2013 | 1/25/2013 | 1/25/2013 | P | PASS |
Eric Strole
|
|
|
no sign-off card posted.
|
Final | 1/23/2013 | 1/24/2013 | 1/24/2013 | A | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Final | 1/14/2013 | 1/14/2013 | 1/14/2013 | P | PART |
Eric Strole
|
|
|
***PARTIAL FINAL ONLY*** for east & west wings. If questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-east and west wing pass.
|
Other | 1/9/2013 | 1/10/2013 | 1/10/2013 | P | DONE |
Eric Strole
|
|
|
1:00 pm-this was a conferance on backflows required.
|
Other | 1/9/2013 | 1/9/2013 | 1/9/2013 | P | DONE |
Eric Strole
|
|
|
PARTIAL FINAL ONLY. If questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-This was a walk-thru
|
Plumbing Rough-in | 10/30/2012 | 10/30/2012 | 10/30/2012 | P | PASS |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-rough-in complete
|
Plumbing Rough-in | 10/22/2012 | 10/22/2012 | 10/22/2012 | P | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-partial water mains pass.
|
Plumbing Rough-in | 10/10/2012 | 10/10/2012 | 10/10/2012 | P | PASS |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Groundwork | 10/10/2012 | 10/10/2012 | 10/10/2012 | P | PASS |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Plumbing Rough-in | 9/27/2012 | 9/28/2012 | 9/28/2012 | P | PART |
Bill VanDegrift
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann west wing water mains ok
|
Plumbing Rough-in | 9/24/2012 | 9/25/2012 | 9/25/2012 | A | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-all inwall water pass.
|
Plumbing Rough-in | 9/20/2012 | 9/21/2012 | 9/21/2012 | A | PART |
Daryl Spivey
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann waste and vent all tested.............ds
|
Plumbing Rough-in | 9/17/2012 | 9/17/2012 | 9/17/2012 | P | PART |
Bill VanDegrift
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann test on water mains in east hall ok
|
Plumbing Rough-in | 9/11/2012 | 9/12/2012 | 9/12/2012 | A | PART |
Daryl Spivey
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Plumbing Rough-in | 8/29/2012 | 8/29/2012 | 8/29/2012 | P | PART |
Eric Strole
|
|
|
if questions please call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-2-sinks in nurses station pass.
|
Plumbing Rough-in | 8/23/2012 | 8/24/2012 | 8/24/2012 | A | PART |
Eric Strole
|
|
|
if questions call gary at ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Plumbing Rough-in | 8/1/2012 | 8/1/2012 | 8/1/2012 | P | PART |
Eric Strole
|
|
|
Waste & Vent. If questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-dwv complete except 2-sinks.
|
Roof Drains | 7/18/2012 | 7/19/2012 | 7/19/2012 | A | PASS |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-roof drains pass
|
Plumbing Rough-in | 7/10/2012 | 7/11/2012 | 7/11/2012 | P | PART |
Daryl Spivey
|
|
|
SOUTH Side of bldg. If questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann south side water tested ok...........ds
|
Plumbing Rough-in | 7/10/2012 | 7/11/2012 | 7/11/2012 | A | PART |
Daryl Spivey
|
|
|
NORTH Side of bldg. If questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann water tested ok north side.......ds
|
Plumbing Rough-in | 6/21/2012 | 6/21/2012 | 6/21/2012 | P | PART |
Eric Strole
|
|
|
west wing rooms pass.
|
Plumbing Rough-in | 6/20/2012 | 6/21/2012 | 6/21/2012 | A | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-dwv in west wing pass. water in the north side of west wing pass.
|
PLM-Aging Inspection | 6/4/2012 | 6/4/2012 | 6/4/2012 | | PART |
Eric Strole
|
|
|
wip
|
Roof Drains | 3/5/2012 | 3/6/2012 | 3/6/2012 | P | PART |
Eric Strole
|
|
|
all dwv and roof drains in slab complete.
|
Groundwork | 3/5/2012 | 3/5/2012 | 3/5/2012 | P | PART |
Eric Strole
|
|
|
dwv in slab complete, have roof drains in slab to complete.
|
Groundwork | 3/2/2012 | 3/2/2012 | 3/5/2012 | P | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-cannot have combination waste and vent in kitchen, gary to change and will reinspect this afternoon.section of dwv complete marked on plans.
|
Groundwork | 2/27/2012 | 2/28/2012 | 2/28/2012 | A | PART |
Eric Strole
|
|
|
test on sections of dwv marked on plans pass
|
Groundwork | 2/27/2012 | 2/27/2012 | 2/27/2012 | P | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-section complete marked on plans. ok to cover as long as test holds for inspection in mourning.
|
Water and/or Sewer | 2/27/2012 | 2/27/2012 | 2/27/2012 | P | PASS |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-waterline pass.
|
Groundwork | 2/20/2012 | 2/21/2012 | 2/21/2012 | A | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-section complete is marked on plans.
|
Groundwork | 2/13/2012 | 2/14/2012 | 2/14/2012 | P | PART |
Eric Strole
|
|
|
section complete is marked on plans.
|
Groundwork | 2/13/2012 | 2/14/2012 | 2/14/2012 | A | PART |
Eric Strole
|
|
|
section complete is marked on plans.
|
Groundwork | 2/10/2012 | 2/13/2012 | 2/13/2012 | A | PART |
Eric Strole
|
|
|
if questions please call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-section complete is marked on plans.
|
Groundwork | 2/7/2012 | 2/8/2012 | 2/8/2012 | P | PART |
Eric Strole
|
|
|
section complete is marked on plans.
|
Groundwork | 2/7/2012 | 2/7/2012 | 2/7/2012 | P | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-sections complete are marked on plans.
|
Groundwork | 2/7/2012 | 2/7/2012 | 2/7/2012 | P | CANC |
Eric Strole
|
|
|
|
Groundwork | 2/6/2012 | 2/7/2012 | 2/7/2012 | A | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-sections complete is marked on plans.
|
Groundwork | 1/31/2012 | 2/1/2012 | 2/1/2012 | A | PART |
Eric Strole
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-trunk line for building drain off east side sewer pass.
|
Other | 1/30/2012 | 1/31/2012 | 1/31/2012 | P | PASS |
Eric Strole
|
|
|
24 hr test on grease interceptor. 24 hr test pass.
|
Groundwork | 1/30/2012 | 1/31/2012 | 1/31/2012 | A | PART |
Jim Johnson
|
|
|
if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann sewer and grease trunk line test ok
|
Other | 1/30/2012 | 1/30/2012 | 1/30/2012 | P | PART |
Eric Strole
|
|
|
Grease trap inspection. if questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-start of 24 hr test on grease interceptor.
|
Groundwork | 1/26/2012 | 1/27/2012 | 1/27/2012 | P | PART |
Eric Strole
|
|
|
LATE PM. If questions call Gary @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann-piping upstream and downstream of grease interceptor pass, still need 24 hr test on grease interceptor.
|