Sprinkler (Final) | 10/20/2011 | 10/20/2011 | 10/20/2011 | P | PASS |
Daryl Spivey
|
|
|
clive Phone #: ###-####
|
Sprinkler (Final) | 10/17/2011 | 10/18/2011 | 10/18/2011 | A | FAIL |
Jim Johnson
|
|
|
clive or monica Phone #: ###-#### need to remove 100 psi piping and replace with 160 psi piping upc 603.4.22 stop and waste valves shall not be installed under ground need to replace with an approved shut off and drain valve need to have double check tested and certified need to provide a blow out tee downstrem of double check left correction notice on site called contractor and left message on phone contractor to recall when ready
|