Final | 5/31/2012 | 5/31/2012 | 5/31/2012 | P | PASS |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Branden Steers
|
Final | 5/30/2012 | 5/30/2012 | 5/30/2012 | P | FAIL |
Jim Johnson
|
|
|
brandon Phone #: ###-#### 1. pex tubing shall not be installed with in the first eighteen (18) inches of piping connected to a water heater.604.11.2 . 2. need 120 dregee hot water limitation on lavatory 414.1 3. need open front seat on water closet 409.2.3 4.need to caulk drinking fountain at wall 408.2 connection notice on site contractor to recall when ready
|
Plumbing Rough-in | 4/23/2012 | 4/23/2012 | 4/23/2012 | P | PASS |
Jim Johnson
|
|
|
BRANDON Phone #: ###-####
|
Groundwork | 4/9/2012 | 4/9/2012 | 4/9/2012 | P | PASS |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Branden Steers
|