Final | 7/10/2012 | 7/11/2012 | 7/11/2012 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### >> Inspection requested via web by Erin Whiting
|
Plumbing Rough-in | 5/11/2012 | 5/11/2012 | 5/11/2012 | P | PASS |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Erin Whiting
|
Plumbing Rough-in | 5/10/2012 | 5/10/2012 | 5/10/2012 | P | FAIL |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Erin Whiting test failed on D W V leak on 3 inch san tee with side inlet on west end resrroom as per upc 2003 909.0 an accessible clean out shall be installed in vertical portion of the foot vent contractor to recall when ready left correction notice on site
|
Water and/or Sewer | 5/8/2012 | 5/9/2012 | 5/9/2012 | P | FAIL |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Erin Whiting air admittance valves (A.A.V.) may be used on true island fixtures only need to repipe kit sink with an approved drain and vent contractor to recall when ready correction notice on site
|