DOC - Permit Finaled | 7/5/2012 | 7/5/2012 | 7/5/2012 | P | PASS |
Eric Strole
|
|
|
|
Water and/or Sewer | 7/5/2012 | 7/5/2012 | 7/5/2012 | P | PASS |
Eric Strole
|
|
|
|
Water and/or Sewer | 7/2/2012 | 7/2/2012 | 7/2/2012 | P | PART |
Eric Strole
|
|
|
ok to cover, pvb needs tested and certified.
|
Water and/or Sewer | 6/29/2012 | 7/2/2012 | 7/2/2012 | A | FAIL |
Eric Strole
|
|
|
Contact tech for access or questions. Phone #: ###-#### >> Inspection requested via web by Amanda Drake-hoseclamps need to be 180 from each other, copper male adapt cannot be used with pvc female adapt and pvb needs tested and certified.
|
Water and/or Sewer | 6/29/2012 | 6/29/2012 | 6/29/2012 | P | CANC |
Eric Strole
|
|
|
Contact tech for access, later in the afternoon if possible Phone #: ###-#### >> Inspection requested via web by Amanda Drake Inspection cancelled from web by: Amanda Drake
|