Final | 12/12/2012 | 12/13/2012 | 12/13/2012 | A | PASS |
Jim Johnson
|
|
|
JOB # 16548. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Plumbing Rough-in | 10/25/2012 | 10/26/2012 | 10/26/2012 | P | PASS |
Jim Johnson
|
|
|
JOB # 16548. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Plumbing Rough-in | 10/24/2012 | 10/25/2012 | 10/25/2012 | P | FAIL |
Jim Johnson
|
|
|
JOB # 16548. Phone #: ###-#### >> Inspection requested via web by Ann Marie ReyesIdaho State Plumbing code 2009 905.5 the vent opening from soil or waste pipe shall not be below the weir of the trap need to repipe trap arm in tub in main bathroom on west side of building contractor to recall when ready correction notice on site
|