Final | 11/14/2013 | 11/15/2013 | 11/15/2013 | A | PASS |
Daryl Spivey
|
|
|
JOB CONTACT IS JOSH Phone #: ###-#### >> Inspection requested via web by ADAM WARR
|
Final | 11/4/2013 | 11/5/2013 | 11/4/2013 | A | CANC |
Daryl Spivey
|
|
|
JOB CONTACT IS COLIN Phone #: ###-#### >> Inspection requested via web by ADAM WARR Inspection cancelled from web by: ADAM WARR
|
Other | 9/24/2013 | 9/24/2013 | 9/24/2013 | P | FAIL |
Bill VanDegrift
|
|
|
pipe cooling tower drainage to sanitary sewer. left correction notice.
|
Plumbing Rough-in | 9/16/2013 | 9/17/2013 | 9/17/2013 | A | PART |
Daryl Spivey
|
|
|
JOB CONTACT - JOSH ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER roof drain inspection completed.......ds
|
Plumbing Rough-in | 8/20/2013 | 8/21/2013 | 8/21/2013 | A | PART |
Bill VanDegrift
|
|
|
JOB CONTACT - JOSH ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER roof drains overflows and floor drain venting in penthouse tests ok
|
Plumbing Rough-in | 7/31/2013 | 8/1/2013 | 8/1/2013 | A | PART |
Daryl Spivey
|
|
|
Josh ###-#### penthouse boiler room wall vents tested ok......ok to cover...........ds
|
Plumbing Rough-in | 7/30/2013 | 7/31/2013 | 7/31/2013 | P | FAIL |
Daryl Spivey
|
|
|
JOB CONTACT - JOSH ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER penthouse venting not holding a test.....ds
|
Roof Drains | 6/24/2013 | 6/25/2013 | 6/25/2013 | A | PART |
Daryl Spivey
|
|
|
JOB CONTACT - JOSH ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER north side primary from 5th floor up to top floor tested ok.......ds
|
Plumbing Rough-in | 6/20/2013 | 6/20/2013 | 6/20/2013 | P | PART |
Daryl Spivey
|
|
|
contact is Keith ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS roof drains from 5th floor to 18th floor on east (8th street side) tested ok..........ds
|
Plumbing Rough-in | 5/23/2013 | 5/24/2013 | 5/24/2013 | P | PART |
Daryl Spivey
|
|
|
JOB CONTACT - KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER 16th, 17th and penthouse roughin ok..........ds
|
Plumbing Rough-in | 5/1/2013 | 5/1/2013 | 5/1/2013 | P | PART |
Daryl Spivey
|
|
|
conact is Keith ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS 16th floo restrooms ok.........8,9,16 floor showers tested ok,..............service sinks from 10th floor thru 16th tested ok............ds
|
Plumbing Rough-in | 4/29/2013 | 4/29/2013 | 4/29/2013 | P | CANC |
Daryl Spivey
|
|
|
Keith Phone #: ###-#### xcd by Keith called...........ds
|
Plumbing Rough-in | 4/17/2013 | 4/18/2013 | 4/18/2013 | P | PART |
Daryl Spivey
|
|
|
JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR 15th floor restroom and 6,7,9,10,11,12,14 and15th floor showers tested ok.....ds
|
Plumbing Rough-in | 4/11/2013 | 4/12/2013 | 4/12/2013 | A | PART |
Daryl Spivey
|
|
|
JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR overflow drains tested from 6th floor down.........ds
|
Plumbing Rough-in | 4/10/2013 | 4/10/2013 | 4/10/2013 | P | PART |
Daryl Spivey
|
|
|
CONTACT IS KEITH ###-####. PLUMBING ROUGH IN INSPECTION ON STORM DRAINS Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS main roof drains from 6th floor down to 1st floor tested..........ds
|
Plumbing Rough-in | 4/2/2013 | 4/3/2013 | 4/3/2013 | P | PART |
Daryl Spivey
|
|
|
JOB CONTACT - KEITH ###-#### 13TH AND 14TH FLOOR Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER 13 & 14th floor restrooms and parking gsrage drains tested ok..........ds
|
Plumbing Rough-in | 3/20/2013 | 3/21/2013 | 3/20/2013 | A | PART |
Daryl Spivey
|
|
|
CONTACT IS KEITH ###-#### INSPECTION IS FOR 12TH FLOOR Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS 12th floor restroom tested ok........correction notice was given for installing incorrect dcva's on potable water service.........ds
|
Plumbing Rough-in | 3/20/2013 | 3/21/2013 | 3/20/2013 | A | CANC |
Daryl Spivey
|
|
|
contact is keith ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS Inspection cancelled from web by: LENNIE BUSS
|
Plumbing Rough-in | 3/14/2013 | 3/14/2013 | 3/14/2013 | A | PART |
Daryl Spivey
|
|
|
11th floor restrooms tested ok............ds
|
Groundwork | 3/14/2013 | 3/14/2013 | 3/14/2013 | A | CANC |
Daryl Spivey
|
|
|
11TH FLOOR REINSPECTION FOR UNDERGROUND. CONTACT IS KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS
|
Plumbing Rough-in | 3/13/2013 | 3/13/2013 | 3/13/2013 | P | CANC |
Daryl Spivey
|
|
|
11TH FLOOR ROUGH IN. JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR xcld will reschedule when lift is operational.
|
Plumbing Rough-in | 3/6/2013 | 3/7/2013 | 3/7/2013 | A | PART |
Daryl Spivey
|
|
|
CONTACT IS KEITH ###-#### INSPECTION IS FOR 10TH FLOOR Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS 10th floor restroom and mop sinks tested ok up to 10th floor.......ds
|
Plumbing Rough-in | 3/1/2013 | 3/1/2013 | 3/1/2013 | P | PART |
Daryl Spivey
|
|
|
contact is Keith ###-#### would like inspection @ 1:00 if possible. thank you Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS 9th floor restroom ok............
|
Plumbing Rough-in | 2/28/2013 | 2/28/2013 | 2/28/2013 | P | FAIL |
Daryl Spivey
|
|
|
JOB CONTACT IS KEITH JOHNSON Phone #: ###-#### >> Inspection requested via web by ADAM WARR waste and vent test did not hold............ds
|
Plumbing Rough-in | 2/22/2013 | 2/22/2013 | 2/22/2013 | P | PART |
Daryl Spivey
|
|
|
contact is KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS restrooms on 6, 7, & 8 are tested ok........ds
|
Plumbing Rough-in | 2/20/2013 | 2/21/2013 | 2/21/2013 | P | NR |
Daryl Spivey
|
|
|
CONTACT IS KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS no ispection..........test did not hold......ds
|
Plumbing Rough-in | 2/1/2013 | 2/4/2013 | 2/4/2013 | A | PART |
Daryl Spivey
|
|
|
CONTACT IS KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS rough in for mop sinks from basement thru 5th floor and did visual on shaft piping.....ds
|
Plumbing Rough-in | 1/30/2013 | 1/30/2013 | 1/30/2013 | P | PART |
Daryl Spivey
|
|
|
KEITH IS THE CONTACT. RI FOR 5TH FLOOR Phone #: ###-#### >> Inspection requested via web by ADAM WARR water, waste and vent risers in chase tested ok up to 6th floor........ds
|
Plumbing Rough-in | 1/18/2013 | 1/18/2013 | 1/18/2013 | P | PART |
Daryl Spivey
|
|
|
JOB CONTACT IS KEITH Phone #: ###-#### >> Inspection requested via web by ADAM WARR 1st and 2nd floor restrooms tested ok.....ds
|