Final | 6/11/2015 | 6/12/2015 | 6/12/2015 | A | PASS |
Eric Strole
|
|
|
AB IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
PLM-Aging Inspection | 4/28/2015 | 4/28/2015 | 4/28/2015 | | PART |
Eric Strole
|
|
|
wip
|
Plumbing Rough-in | 1/27/2015 | 1/28/2015 | 1/29/2015 | P | CANC |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 1/27/2015 | 1/28/2015 | 1/28/2015 | A | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-N/E pod 2nd & 3rd flr waterlines in units pass.
|
Plumbing Rough-in | 1/12/2015 | 1/13/2015 | 1/13/2015 | P | PART |
Bill VanDegrift
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER water in units 222-223-24 322-23 422-23 522-23 needs a few nail plates and 3rd floor water north side too close to outside sheeting
|
Plumbing Rough-in | 12/31/2014 | 1/2/2015 | 1/2/2015 | A | PART |
Eric Strole
|
|
|
north west pod r/i complete
|
Plumbing Rough-in | 12/30/2014 | 12/31/2014 | 12/31/2014 | A | NR |
Eric Strole
|
|
|
call Ab
|
Plumbing Rough-in | 12/29/2014 | 12/30/2014 | 12/30/2014 | P | CANC |
Bill VanDegrift
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER leaks
|
Plumbing Rough-in | 12/29/2014 | 12/30/2014 | 12/30/2014 | A | PART |
Bill VanDegrift
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER north west pod floor 2 and 3 water system test ok
|
Plumbing Rough-in | 12/15/2014 | 12/15/2014 | 12/15/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-North-West pod water mains into units pass.
|
Plumbing Rough-in | 11/25/2014 | 11/26/2014 | 11/28/2014 | P | PART |
Eric Strole
|
|
|
Tower 1 rough-in pass.
|
Plumbing Rough-in | 11/25/2014 | 11/25/2014 | 11/25/2014 | P | CANC |
Eric Strole
|
|
|
|
Plumbing Rough-in | 11/21/2014 | 11/25/2014 | 11/25/2014 | P | CANC |
Eric Strole
|
|
|
CONTACT IS AB ###-#### Phone #: ###-#### Inspection requested via web by MARGGIE BUSS
|
Plumbing Rough-in | 11/21/2014 | 11/25/2014 | 11/25/2014 | A | CANC |
Eric Strole
|
|
|
CONTACT IS AB ###-#### Phone #: ###-#### Inspection requested via web by MARGGIE BUSS
|
Plumbing Rough-in | 11/21/2014 | 11/24/2014 | 11/24/2014 | P | PART |
Eric Strole
|
|
|
CONTACT IS AB ###-#### Phone #: ###-#### Inspection requested via web by MARGGIE BUSS-All water in tower 1 1st thru 5th flr water pass.
|
Plumbing Rough-in | 11/21/2014 | 11/24/2014 | 11/24/2014 | A | PART |
Eric Strole
|
|
|
CONTACT IS AB ###-#### Phone #: ###-#### Inspection requested via web by MARGGIE BUSS-Tower 1 4th flr test on water pass. Rooms 232,233,235,332,333,335,432,433,535,532,533,535 test on dwv pass.
|
Plumbing Rough-in | 11/21/2014 | 11/21/2014 | 11/21/2014 | P | PART |
Eric Strole
|
|
|
Tower 1 5th flr water in units pass
|
Plumbing Rough-in | 11/19/2014 | 11/21/2014 | 11/21/2014 | P | CANC |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 11/21/2014 | 11/21/2014 | 11/21/2014 | A | CANC |
Eric Strole
|
|
|
|
Plumbing Rough-in | 11/19/2014 | 11/20/2014 | 11/20/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Tower 1 all flrs on east side water pass.
|
Plumbing Rough-in | 11/19/2014 | 11/20/2014 | 11/20/2014 | A | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Tower 1 south end flrs 1 thru 5 test on dwv pass.
|
Plumbing Rough-in | 11/18/2014 | 11/19/2014 | 11/19/2014 | A | PART |
Eric Strole
|
|
|
Tower 1 east side 4th flr units test on water pass.
|
Plumbing Rough-in | 11/18/2014 | 11/18/2014 | 11/18/2014 | P | FAIL |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Need to be 6" above flood level rim before tieing into vent stack.
|
Plumbing Rough-in | 11/12/2014 | 11/14/2014 | 11/14/2014 | P | CANC |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 11/12/2014 | 11/13/2014 | 11/13/2014 | P | CANC |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 11/10/2014 | 11/12/2014 | 11/12/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Tower 1, 3rd flr test on water in units 231 & 233 pass.
|
Plumbing Rough-in | 11/10/2014 | 11/12/2014 | 11/12/2014 | A | CANC |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 11/10/2014 | 11/10/2014 | 11/10/2014 | P | NR |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 11/5/2014 | 11/7/2014 | 11/7/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Tower 1 3rd flr units 335,337 test on water pass
|
Plumbing Rough-in | 11/5/2014 | 11/7/2014 | 11/7/2014 | A | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Podium eastside 1st flr test on water pass.
|
Plumbing Rough-in | 11/6/2014 | 11/7/2014 | 11/7/2014 | A | CANC |
Eric Strole
|
|
|
|
Plumbing Rough-in | 11/5/2014 | 11/6/2014 | 11/6/2014 | P | NR |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
Plumbing Rough-in | 11/5/2014 | 11/6/2014 | 11/6/2014 | A | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER-Section of roof drains tested are marked on plans.
|
PLM-Aging Inspection | 8/7/2014 | 8/7/2014 | 8/7/2014 | | PART |
Eric Strole
|
|
|
no calls
|
Groundwork | 4/15/2014 | 4/16/2014 | 4/16/2014 | A | PASS |
Eric Strole
|
|
|
Ground work complete, test on water supply pass
|
DOC - Permit Finaled | 4/15/2014 | 4/15/2014 | 4/15/2014 | P | PASS |
Eric Strole
|
|
|
|
Groundwork | 4/15/2014 | 4/15/2014 | 4/15/2014 | P | PART |
Eric Strole
|
|
|
contact is Ab ###-#### Phone #: ###-#### >> Inspection requested via web by LENNIE BUSS-All underground dwv test pass. Still need water supply.
|
Groundwork | 4/11/2014 | 4/11/2014 | 4/11/2014 | A | PART |
Eric Strole
|
|
|
section complete is marked on plans
|
Groundwork | 4/10/2014 | 4/10/2014 | 4/10/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER-1-3" and 1-8" roof drain stub ok to cover
|
Groundwork | 4/3/2014 | 4/3/2014 | 4/3/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT IS AB ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS
|
Groundwork | 4/1/2014 | 4/2/2014 | 4/2/2014 | P | PART |
Eric Strole
|
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER-section complete is marked on plans.
|