Final | 8/24/2015 | 8/25/2015 | 8/25/2015 | A | PASS |
Eric Strole
|
|
|
please call Jake with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Final | 8/14/2015 | 8/17/2015 | 8/17/2015 | A | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige-2nd , 3rd & 4th flr final complete.
|
Final | 8/14/2015 | 8/14/2015 | 8/14/2015 | P | PART |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige temp occ on floors 2,3 and 4 ok
|
Final | 8/13/2015 | 8/14/2015 | 8/14/2015 | A | CANC |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige >cancelled per jake
|
Final | 8/12/2015 | 8/13/2015 | 8/13/2015 | A | NR |
Jim Little
|
|
|
|
Final | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | NR |
Eric Strole
|
|
|
Not ready
|
Final | 8/10/2015 | 8/11/2015 | 8/11/2015 | A | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige-4th flr units 401 thru 407 & 409 thru 415 pass.
|
Final | 8/10/2015 | 8/10/2015 | 8/10/2015 | P | PART |
Eric Strole
|
|
|
please let jake know if you have any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-2nd flr final complete.
|
Final | 8/7/2015 | 8/7/2015 | 8/7/2015 | A | PART |
Eric Strole
|
|
|
Units 301 thru 317. 344, 343 pass
|
Water and/or Sewer | 8/7/2015 | 8/7/2015 | 8/7/2015 | A | CANC |
Eric Strole
|
|
|
|
Final | 8/6/2015 | 8/7/2015 | 8/7/2015 | A | FAIL |
Eric Strole
|
|
|
Units 218,220,318,320,418,420,518,520 water heaters are under sized per the 2009 ISPC table 5-1. Need a minimum of a 67 1st hr recovery rate.
|
Final | 8/5/2015 | 8/6/2015 | 8/6/2015 | A | NR |
Eric Strole
|
|
|
this is a partial final for 3rd floor east Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Final | 8/4/2015 | 8/5/2015 | 8/5/2015 | A | FAIL |
Eric Strole
|
|
|
2nd floor east Partial final Phone #: ###-#### Inspection requested via web by Nicholas Paige-Units 243 thru 244 fail, water heaters are undersized.
|
Final | 8/4/2015 | 8/4/2015 | 8/4/2015 | P | FAIL |
Bill VanDegrift
|
|
|
water heaters installed do not meet the first hour rating of ISPC table 501
|
Final | 8/3/2015 | 8/4/2015 | 8/4/2015 | A | FAIL |
Eric Strole
|
|
|
final for 2nd floor east Wing only Phone #: ###-#### Inspection requested via web by Nicholas Paige-Units 201 thru 218 water heaters are under sized. (2 bath 4 bedroom require a 67 gallon first hour recovery rate and a 4 bath 4 bedroom requires a 80 gallon first hour recovery rate.)
|
Plumbing Rough-in | 5/27/2015 | 5/28/2015 | 5/28/2015 | A | PART |
Eric Strole
|
|
|
overheads- please call jake with any questions. Phone #: ###-#### Inspection requested via web by Nicholas Paige-Hangers in garage overhead pass
|
Plumbing Rough-in | 5/26/2015 | 5/26/2015 | 5/26/2015 | P | PASS |
Eric Strole
|
|
|
please call Jake with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-East wing rough-in complete.
|
Water and/or Sewer | 5/21/2015 | 5/22/2015 | 5/22/2015 | P | PART |
Eric Strole
|
|
|
Call jake with queations Phone #: ###-#### Inspection requested via web by Nicholas Paige-DWV in units 417,517 pass. Test on water in units 515,516,518 pass.
|
Plumbing Rough-in | 5/21/2015 | 5/22/2015 | 5/22/2015 | A | PART |
Eric Strole
|
|
|
Test on water in units 514,511,512,513,542,543 pass. Test on dwv in units 411,412,413,414,415,416,417,511,513,513,514,515,516,517,518,418 pass.
|
Plumbing Rough-in | 5/21/2015 | 5/21/2015 | 5/21/2015 | P | CANC |
Eric Strole
|
|
|
please call jake if u have questions Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Plumbing Rough-in | 5/21/2015 | 5/21/2015 | 5/21/2015 | A | CANC |
Eric Strole
|
|
|
|
Plumbing Rough-in | 5/20/2015 | 5/21/2015 | 5/21/2015 | A | PART |
Eric Strole
|
|
|
please call jake with questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-Test on dwv in units 409,410,442,443,444,509,510,542,543,544 pass. Test on water in units 507,508,509,510, 544 pass. Test on mains pass.
|
Plumbing Rough-in | 5/20/2015 | 5/20/2015 | 5/20/2015 | P | CANC |
Eric Strole
|
|
|
|
Water and/or Sewer | 5/20/2015 | 5/20/2015 | 5/20/2015 | P | CANC |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Plumbing Rough-in | 5/19/2015 | 5/20/2015 | 5/20/2015 | A | PART |
Eric Strole
|
|
|
please let jake know if you have any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-Test on DWV in units 404,405,406,407,408,504,505,506,507,508 pass. Test on water in units 501,502,503,504,505,506 pass.
|
Plumbing Rough-in | 5/15/2015 | 5/18/2015 | 5/18/2015 | A | PART |
Eric Strole
|
|
|
please call jake with any questions. Phone #: ###-#### Inspection requested via web by Nicholas Paige-Test on water and dwv in units 401,402,403 pass. Test on dwv in units 501,502,503 pass.
|
Plumbing Rough-in | 5/13/2015 | 5/14/2015 | 5/14/2015 | A | PART |
Eric Strole
|
|
|
2nd and 3rd flr units rough-in complete
|
Plumbing Rough-in | 5/12/2015 | 5/12/2015 | 5/12/2015 | P | PART |
Eric Strole
|
|
|
DWV in units 320,319,318,317,316,315,314,313,312,311,310,309 pass. Test on water in units 415,414,413,412,411,410,409,407,406,405,404,403,402,444,443,442 pass.
|
Plumbing Rough-in | 5/11/2015 | 5/11/2015 | 5/12/2015 | P | FAIL |
Eric Strole
|
|
|
please call jake with any question. this is for the east wing Phone #: ###-#### Inspection requested via web by Nicholas Paige-Test on water in units 430,429,428,427,426,425,424,423,422,421,420,419,418,417,416 pass. Waste in units 320,319,318,317,316,315,314,313,312,311,310,309 fail.Need to fix all flat and backgraded dwv and retest.
|
Water and/or Sewer | 4/24/2015 | 4/27/2015 | 4/27/2015 | A | CANC |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Plumbing Rough-in | 4/23/2015 | 4/23/2015 | 4/23/2015 | P | PART |
Eric Strole
|
|
|
please call jake with any questions. this is an east side partial rough in Phone #: ###-#### Inspection requested via web by Nicholas Paige-Test on dwv & water in units 242,243,244 pass. Test on water in units 342,343,344 pass.
|
Other | 4/16/2015 | 4/17/2015 | 4/17/2015 | A | PART |
Bill VanDegrift
|
|
|
onsite conference inspection for tomorrow am to talk about island venting with plumbing inspector. Please note that we would like Eric Strole and Bill Vandegrift to attend and meet Jake. Phone #: ###-#### Inspection requested via web by Nicholas Paige
went over island sink venting. only approved on true island sinks, continue with island sink venting on the rest.
|
Plumbing Rough-in | 4/15/2015 | 4/16/2015 | 4/16/2015 | P | PART |
Eric Strole
|
|
|
Units 201 thru 220 rough-in pass. Units 301 thru 320 water test pass.
|
Plumbing Rough-in | 4/15/2015 | 4/15/2015 | 4/15/2015 | P | PART |
Eric Strole
|
|
|
please call jake for questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-Units 201,202,203 0k for cover.
|
Plumbing Rough-in | 4/6/2015 | 4/7/2015 | 4/7/2015 | A | PART |
Eric Strole
|
|
|
please call Jake with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-DWV & water test pass and ok to cover lids only in units 207,208,209,210,211,212. Need bottom plate nailplates.Test on water in units 307,308,309,310,311,312 pass.
|
Plumbing Rough-in | 3/31/2015 | 4/1/2015 | 4/1/2015 | A | PART |
Eric Strole
|
|
|
NE 2nd floor Rough In inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige-Test on water in units 201,202,203,204,205,206 pass.OK to cover lids in those unit only. Need to cut san tees out of kitcken stacks and cap off extra 2" waste lines.Need to fix leaks on dwv in those units and nail plate bottom plates. - Test on water in units 301,302,303,304,305 & 306 pass.
|
Plumbing Rough-in | 2/24/2015 | 2/25/2015 | 2/25/2015 | A | PART |
Eric Strole
|
|
|
Please call jake with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-Corridors east side 1st flr ok to rock 24" down.
|
Other | 1/27/2015 | 1/28/2015 | 1/28/2015 | A | DONE |
Eric Strole
|
|
|
conference to discuss manifold connections. mock up is done Phone #: ###-#### Inspection requested via web by Nicholas Paige-Conferance,Need to seperate waterlines so not rubbing against wood.
|
Water and/or Sewer | 12/11/2014 | 12/11/2014 | 12/11/2014 | P | PART |
Eric Strole
|
|
|
under ground interceptor vent inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige-Ground work is complete
|
Water and/or Sewer | 12/9/2014 | 12/10/2014 | 12/10/2014 | P | PART |
Daryl Spivey
|
|
|
24 hr test on flammable intercepter ok..........ds
|
Groundwork | 12/8/2014 | 12/9/2014 | 12/9/2014 | P | PART |
Eric Strole
|
|
|
please call Jake with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-ground work complete except vents for interceptor.
|
Groundwork | 12/3/2014 | 12/4/2014 | 12/4/2014 | P | PART |
Eric Strole
|
|
|
please call jake with any questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-Section complete is marked on plans.
|
Water and/or Sewer | 12/2/2014 | 12/2/2014 | 12/2/2014 | P | PART |
Eric Strole
|
|
|
this is a water main inspection. please call jake with any questions. Phone #: ###-#### Inspection requested via web by Nicholas Paige-Water supply stub in and out of building ok.
|
Other | 11/26/2014 | 11/26/2014 | 11/28/2014 | P | DONE |
Eric Strole
|
|
|
This stainless steel piping has no testing agency approval marking on pipe except a number from table 6-4 of 2009 ISPC minus the testing agency marking and has no other approval markings and no installation instructions. Bill Vandegrift has a paper of a mill testing and has approved this piping for the potable water system and I am supposed to get installation instructions from the manufacturer.
|
Other | 11/26/2014 | 11/26/2014 | 11/28/2014 | P | PASS |
Bill VanDegrift
|
|
|
2pm went over the stainless piping. Bill Carter will provide installation standards. Mill test seems correct for material.
|
Water and/or Sewer | 11/21/2014 | 11/24/2014 | 11/25/2014 | A | CANC |
Eric Strole
|
|
|
this is a conference email aswell to discuss ss pipe. Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Water and/or Sewer | 11/21/2014 | 11/21/2014 | 11/21/2014 | P | FAIL |
Eric Strole
|
|
|
Stainless needs listing
|
Groundwork | 11/21/2014 | 11/21/2014 | 11/21/2014 | A | PART |
Eric Strole
|
|
|
Call doran with questions Phone #: ###-#### Inspection requested via web by Nicholas Paige-section complete is marked on plans
|
Other | 11/18/2014 | 11/19/2014 | 11/19/2014 | A | DONE |
Eric Strole
|
|
|
This was a conferance
|
Other | 11/17/2014 | 11/18/2014 | 11/18/2014 | P | CANC |
Eric Strole
|
|
|
|