Final | 10/7/2015 | 10/8/2015 | 10/8/2015 | A | PASS |
Jim Little
|
|
|
Kyle// please call for access Phone #: ###-####
|
Final | 10/1/2015 | 10/2/2015 | 10/2/2015 | P | FAIL |
Eric Strole
|
|
|
Tyler Phone #: ###-####-Need to use approved material for T&P line & need to caulk toilets.
|
Final | 9/29/2015 | 9/30/2015 | 9/30/2015 | A | FAIL |
Jim Little
|
|
|
Kyle Phone #: ###-#### >pan under gas water heater must be metal. >pipe t&p from water heater to garage floor >caulk water closets to floor >redo kitchen sink trap, it is a running trap and installed backwards >anchor dw >anchor hose bibbs
|
Plumbing Rough-in | 7/2/2015 | 7/6/2015 | 7/6/2015 | A | PASS |
Eric Strole
|
|
|
Kyle Phone #: ###-####
|