Permit Information
Permit NumberPLM15-02389
StatusFinaled
Name BYERS PLUMBING & MECHANICAL LLC
Site Address 1612 S BROADWAY AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install plumbing for 2 bathrooms and kitchen
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/9/201510/9/201510/9/2015PPASS
DetailsEric Strole
Backflow has been added Phone #: ###-#### Inspection requested via web by MICHAEL BYERS
Final9/28/20159/28/20159/28/2015APART
DetailsEric Strole
All work is complete Phone #: ###-#### Inspection requested via web by MICHAEL BYERS-Need to have all equipment installed before final. Temp final ok.
Final9/25/20159/25/20159/25/2015PPART
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by MICHAEL BYERS-Temp final ok.
Final9/25/20159/25/20159/25/2015PCANC
DetailsEric Strole
Final9/24/20159/24/20159/25/2015PFAIL
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by MICHAEL BYERS-Need to seperate ice makers & hot water dispensors from the same rpba. Need to add a dbca on vegetable defroster. Need tempered water to all public lavs & hand sinks. T&P lines need an airgap. Need a seperate water line for the soap dispensor at the mop sink. Need to run drain for vegetable defroster & fernco's are only approved for below grade.
Plumbing Rough-in8/6/20158/6/20158/6/2015PPASS
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by MICHAEL BYERS
Groundwork7/24/20157/24/20157/24/2015PPASS
DetailsEric Strole
Grease interceptor piping only Phone #: ###-#### Inspection requested via web by MICHAEL BYERS-piping at interceptor pass
Groundwork7/16/20157/17/20157/17/2015APASS
DetailsEric Strole
Groundwork7/16/20157/16/20157/16/2015ACANC
DetailsEric Strole
Groundwork7/16/20157/16/20157/16/2015PPART
DetailsEric Strole
Phone #: ###-#### Inspection requested via web by MICHAEL BYERS-Need to use fixture fitting on back to flr drains.