Final | 11/16/2015 | 11/16/2015 | 11/16/2015 | P | PASS |
Jim Little
|
|
|
JOB SITE MANAGER: PAUL THOMPSON ###-#### Phone #: ###-#### Inspection requested via web by Chris Field
|
Plumbing Rough-in | 9/8/2015 | 9/8/2015 | 9/8/2015 | P | PASS |
Jim Little
|
|
|
PAUL THOMPSON, SITE SUPERINTENDENT. Phone #: ###-#### Inspection requested via web by Chris Field >Still missing 4 nail plates, job super on site installed them
|
Plumbing Rough-in | 9/1/2015 | 9/2/2015 | 9/2/2015 | P | FAIL |
Jim Little
|
|
|
PAUL THOMPSON, JOB SUPERVISOR. Phone #: ###-#### Inspection requested via web by Chris Field 1>DWV test failed, below 5psi 2>missing nail plates throughout 3>need support at base of 3" stack 4>bow in hor vent from tub to lavs upstairs 5>rubber fernco in crawl needs to be a shielded coupling 6>water service connection does not appear to be an approved fitting for p.e. pipe. 7>strap water service up from resting on concrete edge.
|
Plumbing Rough-in | 8/28/2015 | 8/31/2015 | 8/31/2015 | A | CANC |
Jim Little
|
|
|
JOB FOREMEN, PAUL THOMPSON, ###-####. Phone #: ###-#### >> Inspection requested via web by Chris Field Inspection cancelled from web by: Chris Field
|