Final | 11/12/2015 | 11/13/2015 | 11/13/2015 | P | PASS |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by Soubanh Senethavialy
|
Plumbing Rough-in | 9/18/2015 | 9/21/2015 | 9/21/2015 | A | PASS |
Daryl Spivey
|
|
|
Re plumb a laundry room to a powder bathroom, add a hose bib, relocate washer box to downstairs bathroom, move toilet, change shower to tub and two sinks. Phone #: ###-#### Inspection requested via web by Soubanh Senethavialy
|