Final | 3/7/2016 | 3/8/2016 | 3/8/2016 | A | PASS |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Powell
|
Final | 3/2/2016 | 3/2/2016 | 3/2/2016 | A | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Powell >Need tempering valve @ public lavatory >need a 1" airgap on t&p >install a S/O valve before DCVA >install S/O valve in occupied side of building. >support mop sink faucet
|
Plumbing Rough-in | 12/11/2015 | 12/11/2015 | 12/11/2015 | P | PASS |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Powell
|
Plumbing Rough-in | 12/9/2015 | 12/10/2015 | 12/10/2015 | P | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Powell >DWV test failed on the bath group. >extend nailplate to corner @ 3" pipe. >water ok, heat trace must be on a thermostat and not exceed 180 degrees
|
Groundwork | 10/7/2015 | 10/8/2015 | 10/8/2015 | A | PASS |
Jim Little
|
|
|
ground work inspection for commercial Phone #: ###-#### Inspection requested via web by Randy Powell
|