Final | 4/20/2016 | 4/21/2016 | 4/21/2016 | A | PASS |
Eric Strole
|
|
|
|
PLM-Aging Inspection | 3/1/2016 | 3/1/2016 | 3/1/2016 | | PART |
Eric Strole
|
|
|
No calls
|
Water and/or Sewer | 10/19/2015 | 10/20/2015 | 10/20/2015 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Brad Crossland-Need to change out fernco in crawl by final.
|
Plumbing Rough-in | 10/16/2015 | 10/16/2015 | 10/16/2015 | P | FAIL |
Eric Strole
|
|
|
Call for any info needed Phone #: ###-#### Inspection requested via web by Brad Crossland-Need to test dwv, Support dwv every 4', Need c/o at kitchen, Need to use an approved transition from pvc to abs, Trap at tub needs to be same size as trap arm, Need to use 5 1/2" nailplates.
|