Final | 12/23/2015 | 12/24/2015 | 12/24/2015 | A | PASS |
Daryl Spivey
|
|
|
Call Robert with any questions or concerns at ###-#### Phone #: ###-#### Inspection requested via web by Ben Davis
|
Final | 12/22/2015 | 12/22/2015 | 12/22/2015 | P | PART |
Eric Strole
|
|
|
CALL ROBERT WITH ANY QUESTIONS OR CONCERNS ###-#### Phone #: ###-#### Inspection requested via web by Ben Davis-DBCA needs tested and certified and need to install a thermal expantion tank. Temp final ok.
|
Final | 12/18/2015 | 12/21/2015 | 12/21/2015 | A | FAIL |
Jim Little
|
|
|
CALL ROBERT WITH ANY QUESTIONS OR CONCERNS ###-#### Phone #: ###-#### Inspection requested via web by Ben Davis >secure and caulk utility sink >T&P on water heater needs to discharge to an approved location, such as outside if no floor drain in area.
|
Plumbing Rough-in | 11/30/2015 | 12/1/2015 | 12/1/2015 | A | PASS |
Eric Strole
|
|
|
CALL SKYLER WITH ANY QUESTIONS OR CONCERNS. ###-#### Phone #: ###-#### Inspection requested via web by Ben Davis
|
Plumbing Rough-in | 11/25/2015 | 11/30/2015 | 11/30/2015 | A | FAIL |
Eric Strole
|
|
|
CALL SKYLER WITH ANY QUESTION ###-#### Phone #: ###-#### Inspection requested via web by Ben Davis-Need isolators on pex lines thru all metal studs per manufacture instuations. Need to fix backgrade on 3". Need to make approved transition from sch 80 to abs. Need to test dwv. Need to group plumbing permit with building permit.
|