Final | 4/20/2016 | 4/21/2016 | 4/21/2016 | A | PASS |
Bill VanDegrift
|
|
|
Inspection requested via web by Brian Johansen
|
Final | 4/18/2016 | 4/19/2016 | 4/19/2016 | A | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Brian Johansen >need grates and strainers @ floor sinks >secure sink to wall >trap sink hooked to grease trap per manfacture installation >reconnect vent on back of house by window >tie flow control vent into venting system unless manufacture shows otherwise
|
Plumbing Rough-in | 3/28/2016 | 3/29/2016 | 3/29/2016 | A | PASS |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by Brian Johansen
|
Plumbing Rough-in | 3/25/2016 | 3/25/2016 | 3/25/2016 | P | FAIL |
Daryl Spivey
|
|
|
230 replumb waste to meet code........D/W not to drain thru grease trap...........ds
|
Plumbing Rough-in | 3/24/2016 | 3/25/2016 | 3/25/2016 | A | PEND |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by Brian Johansen need to meet plumber on site.......ds
|