DOC - Permit Finaled | 8/11/2016 | 8/11/2016 | 8/11/2016 | P | PASS |
Jim Little
|
|
|
|
Water and/or Sewer | 8/3/2016 | 8/3/2016 | 8/3/2016 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by robert dunson
|
Water and/or Sewer | 8/1/2016 | 8/1/2016 | 8/1/2016 | A | CANC |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by robert dunson
|
Sprinkler (Final) | 8/1/2016 | 8/1/2016 | 8/1/2016 | A | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by robert dunson >need to uncover to see tie in >remove threaded ftg from upstream of DCVA so a hose bibb cannot be added, threaded ftg for blowout needs to be downstream of DCVA. >re-test DCVA after repiping
|