Final | 12/27/2016 | 12/27/2016 | 12/27/2016 | P | PASS |
Dan Ediger
|
|
|
The door is 1052 Dan we did not put a double check for the coffee make because they are not going to but on in Let me know if this will work before you come and inspect Thanks rob ###-#### Phone #: ###-#### Inspection requested via web by robert goodson
|
Final | 12/19/2016 | 12/19/2016 | 12/19/2016 | P | PART |
Dan Ediger
|
|
|
0152 Phone #: ###-#### Inspection requested via web by robert goodson. 1. Install a thermal expansion tank on the cold side of the water heater and downstream of the double check valve. 608.3 2. Install a double check valve or RP (per plans), for the commercial coffee maker. 3. Install a temperature limiting device on the public restroom faucet that meets ASSE 1070. 413.1.
|
Plumbing Rough-in | 9/23/2016 | 9/23/2016 | 9/23/2016 | P | PASS |
Eric Strole
|
|
|
|
Water and/or Sewer | 9/23/2016 | 9/23/2016 | 9/23/2016 | P | CANC |
Eric Strole
|
|
|
Code 1052 Phone #: ###-#### Inspection requested via web by robert goodson
|
Groundwork | 8/23/2016 | 8/23/2016 | 8/23/2016 | P | PASS |
Bill VanDegrift
|
|
|
0152 Phone #: ###-#### Inspection requested via web by robert goodson gw ok with access to service connection.
|