Sprinkler (Final) | 10/10/2017 | 10/10/2017 | 10/10/2017 | P | PASS |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by JANET TATILIAN
|
Sprinkler (Final) | 9/1/2017 | 9/1/2017 | 9/1/2017 | P | PART |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by JANET TATILIAN tested ok but can't use green 100psi pipe on potable side.......160 min. pipe or code approved material for potable water......ds
|
PLM-Aging Inspection | 6/29/2017 | 6/29/2017 | 6/29/2017 | | PEND |
Daryl Spivey
|
|
|
went by and dcva has not been tested......called contractor and he will get it certified and call it back in.........Rob 941.8575............ds
|