Permit Information
Permit NumberPLM17-02407
StatusFinaled
Name BUSS MECHANICAL SERVICES INC
Site Address 8800 W EMERALD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: PLUMBING, WASTE AND VENTS, DOMESTIC WATER, FIXTURES// permit for both BLD17-00359 and BLD17-01088
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/13/20188/13/20188/13/2018PPASS
DetailsBill VanDegrift
this permit is for both packages the building permit description references this permit for the ti and package A.
Final7/31/20188/1/20188/1/2018APEND
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. Waiting on medgas reports
Final7/12/20187/13/20187/13/2018APART
DetailsDan Ediger
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Final rough-in was completed on May 29, 2018.
1. All backflow assemblies in the existing building need cerifications due to out of date.
2. Expose the water service tracer wire at the building.
3. Verify all med gas certs have been forwarded to the City of Boise.
Temp occ ok
Plumbing Rough-in5/29/20185/30/20185/30/2018PPART
DetailsDan Ediger
JOHNNY IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Swing room, West break room/rr. ok to cover
Plumbing Rough-in5/7/20185/8/20185/8/2018APASS
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. Operating room sinks (two)
Plumbing Rough-in5/7/20185/7/20185/7/2018PPASS
DetailsDan Ediger
JOHNNY IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. Pharmacy sink
Groundwork5/1/20185/1/20185/1/2018PPASS
DetailsDan Ediger
PLEASE CALL CHAD FOR DIRECTIONS TO WORK. HIS NUMBER IS ###-####. Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Old observation room/new break room sink and restrooms.
Groundwork4/23/20184/24/20184/24/2018PPASS
DetailsDan Ediger
CHAD IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Groundworks in ANSE
Groundwork4/20/20184/23/20184/23/2018PFAIL
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
couldn't locate work. please leave notes as to what I'm to inspect. Could not make connection with Russell.
Groundwork4/19/20184/20/20184/20/2018ACANC
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER Inspection cancelled from web by: BECCA DUMMER
Groundwork4/17/20184/18/20184/18/2018APASS
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Groundwork for one sink Pharmacy, one sink new OR, one sink break room, and one rr in the men's locker room. Adding a 3" end of line cleanout nexst to the lav.
Final3/9/20183/9/20183/9/2018PPART
DetailsDan Ediger
The extended stay rooms are ok to occupy. Hub drain needs to have a trap primer installed.
Final3/7/20183/9/20183/9/2018ANR
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
Final3/6/20183/8/20183/7/2018ACANC
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER Inspection cancelled from web by: BECCA DUMMER
Plumbing Rough-in2/12/20182/13/20182/13/2018PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Clinic sink in wall plumbing ok
Groundwork1/26/20181/29/20181/29/2018PPASS
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
Rough-in for the Nepturne machine drains. ok to cover
Groundwork1/17/20181/18/20181/18/2018PPART
DetailsBill VanDegrift
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER gw for two surgical garbage disposals ok
Plumbing Rough-in12/27/201712/28/201712/28/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
NW hall/center 2 extended stay units ok to cover
Plumbing Rough-in12/26/201712/27/201712/27/2017AFAIL
DetailsDan Ediger
JOB CONTACT - RUSSELL ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
1. Support all shower heads at drop ears.
2. Support all copper at 6' (verify)
3. Nail plate where missing.
Plumbing Rough-in12/20/201712/26/201712/26/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
NW Extended stay 2rms
Med/Gas Systems12/19/201712/20/201712/20/2017PPART
DetailsDan Ediger
Med gas pass 24hr test
Plumbing Rough-in12/19/201712/20/201712/20/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Three southwest extended stay and two center corridor ok to cover.
Plumbing Rough-in12/19/201712/21/201712/20/2017PCANC
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER Inspection cancelled from web by: BECCA DUMMER
Med/Gas Systems12/19/201712/20/201712/19/2017ACANC
DetailsDan Ediger
Water and/or Sewer12/19/201712/20/201712/19/2017ACANC
DetailsDan Ediger
Plumbing Rough-in12/14/201712/19/201712/19/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Start Med Gas pressure test 2:30pm
Plumbing Rough-in12/14/201712/15/201712/15/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Extended stay rooms south wall.
Final12/7/201712/8/201712/8/2017APART
DetailsBill VanDegrift
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
partial occupancy for the mob on the south side. still need to set some equipment in the kitchen and dining area.
Roof Drains11/21/201711/21/201711/21/2017PPASS
DetailsDan Ediger
Plumbing Rough-in11/20/201711/21/201711/21/2017AFAIL
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT 20-###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Roof drains: Two leaks and one backgrade
Plumbing Rough-in11/15/201711/17/201711/17/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. East corridor water and cleanroom ok
Plumbing Rough-in11/9/201711/13/201711/13/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
196/197 ok to cover restrooms. Urinal cleanout to move above the urinal in the access panal
Final11/8/201711/9/201711/9/2017APART
DetailsDan Ediger
THIS IS FOR THE PHARMACY. RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Pharmacy sink is approved
Final10/3/201710/5/201710/5/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Med gas final in New OR #141
Groundwork10/4/201710/4/201710/4/2017APASS
DetailsDan Ediger
Roof drain ground work for the center building west end
Plumbing Rough-in10/2/201710/2/201710/2/2017PPART
DetailsDan Ediger
roof drains ok to cover. Water test complete
Water and/or Sewer10/2/201710/2/201710/2/2017PCANC
DetailsDan Ediger
not scheduled-mistake.
Final9/29/201710/2/201710/2/2017ANR
DetailsDan Ediger
JOB CONTACT - RUSSELL ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
Plumbing Rough-in9/29/201710/2/201710/2/2017ANR
DetailsDan Ediger
JOB CONTACT - RUSSELL ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
Plumbing Rough-in9/28/20179/28/20179/28/2017PPART
DetailsDan Ediger
Area "A" overhead water ok to cover
Plumbing Rough-in9/27/20179/28/20179/28/2017ANR
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
Plumbing Rough-in9/19/20179/20/20179/20/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. Three west sinks and laundry waters ok to cover.
Need test on the lint trap vent and 4" vent riser in the laundry.
Groundwork9/12/20179/13/20179/13/2017APASS
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
Groundwork9/5/20179/6/20179/5/2017APART
DetailsDan Ediger
JOB CONTACT - RUSSELL ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Ground work for the roof drains in the central building.
Groundwork8/31/20179/1/20179/1/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
192-193 and laundry up to the lent trap
Groundwork8/28/20178/29/20178/29/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
166,167, 188, 189 ok to cover.
The hand sink will wet vent on the lent trap in teh laundry
Groundwork8/24/20178/25/20178/25/2017APART
DetailsDan Ediger
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
162.163,158,159,170,171
Groundwork8/24/20178/25/20178/24/2017PCANC
DetailsDan Ediger
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER Inspection cancelled from web by: BECCA DUMMER
Groundwork8/22/20178/23/20178/23/2017APART
DetailsDan Ediger
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
GW 182-184-185-233-237-238 ok to cover
Groundwork8/18/20178/22/20178/22/2017APART
DetailsDan Ediger
JOB CONTACT - RUSSELL ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Extend stay room and center janitor
Plumbing Rough-in8/17/20178/17/20178/17/2017PPART
DetailsDan Ediger
Pressure test on the kitchen dwv top out..
Still nees plate strapped.
PT ok
Plumbing Rough-in8/15/20178/18/20178/17/2017PCANC
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER Inspection cancelled from web by: BECCA DUMMER
Plumbing Rough-in8/16/20178/17/20178/17/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER..
Ground work for the sterile room and east end rr next to the sterile room ok to cover.
The kitchen walls per code; scheduled to come back this afternoon to recheck pressure test.
Plumbing Rough-in8/11/20178/15/20178/14/2017PCANC
DetailsDan Ediger
JOB CONTACT - RUSSELL ###-#### Phone #: ###-#### >> Inspection requested via web by BECCA DUMMER Inspection cancelled from web by: BECCA DUMMER
Groundwork8/8/20178/9/20178/9/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
6" main drain from east to west-out. Branch lines capped.
Plumbing Rough-in8/3/20178/4/20178/4/2017PCANC
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Passed as part medical gas
Med/Gas Systems8/4/20178/4/20178/4/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
New surgical room walls ok to cover/under test.
Retest after running the line extensions.
Groundwork8/1/20178/2/20178/2/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Pharmacy water and waste in the wall ok to cover.
The vent will be run after ductwook install.
The sewer from the grease line not approved. The tank needs the vent hooked up on the outlet side of the interceptor and tested. The santees in the tank will need to be capped on the top but not glued.
Groundwork7/28/20177/31/20177/31/2017ACANC
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Rescheduled as a rough in
Plumbing Rough-in7/31/20177/31/20177/31/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
West wing DWV H2O ok to cover
Groundwork7/24/20177/25/20177/25/2017APART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Fire riser room and rr.
SE corner ok
Other7/18/20177/19/20177/19/2017PCANC
DetailsDan Ediger
complete 24 hour test
Groundwork7/17/20177/18/20177/18/2017PPART
DetailsDan Ediger
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER.
Kitchen plumbing in southeast corner ok to cover.
Grease trap vent to be coredrilled and inspected on rough-in