Water and/or Sewer | 8/9/2017 | 8/10/2017 | 8/10/2017 | A | PASS |
Dan Ediger
|
|
|
complete 24 hour test
|
Final | 8/10/2017 | 8/10/2017 | 8/10/2017 | A | PASS |
Dan Ediger
|
|
|
complete 24 hour test. OK to cover
|
Water and/or Sewer | 8/9/2017 | 8/9/2017 | 8/9/2017 | P | PART |
Dan Ediger
|
|
|
Final sewer connection. Piping ok to cover. Need to finish 24 hour tank test in the am
|
Groundwork | 8/8/2017 | 8/9/2017 | 8/9/2017 | A | PART |
Dan Ediger
|
|
|
Mike Phone #: ###-####. Start 24 hour test on grease interceptor
|
Groundwork | 8/8/2017 | 8/8/2017 | 8/8/2017 | P | PART |
Dan Ediger
|
|
|
Mike Phone #: ###-####. Changed to sewer and water.
|
Water and/or Sewer | 8/8/2017 | 8/8/2017 | 8/8/2017 | P | PART |
Dan Ediger
|
|
|
Mike Phone #: ###-####. Grease line and vent to the tank ok to cover. Sewer ok to cover to grease line. Call for 24hr tank test
|
Water and/or Sewer | 8/7/2017 | 8/7/2017 | 8/7/2017 | P | FAIL |
Dan Ediger
|
|
|
George-Sewer only Phone #: ###-####. The grease interceptor must vent from the outlet side. See drawing provided. There is a section of the sewer, at the transition coupling that is flat
|