Final | 2/27/2018 | 2/27/2018 | 2/27/2018 | P | PASS |
Dan Ediger
|
|
|
Contact Name: Josh Wilson - Please Call Josh for door code. Phone #: ###-#### Inspection requested via web by Melissa Kaae
|
Final | 2/22/2018 | 2/23/2018 | 2/23/2018 | A | FAIL |
Dan Ediger
|
|
|
Contact Name: Josh Wilson PLEASE CALL JOSH FOR DOOR LOCK CODE. Phone #: ###-#### Inspection requested via web by Melissa Kaae. 1. The indirect waste must have an air gap equal to 2x the diameter of the pipe. 2. The chemical feed at the mop sink must have it's own valve or a connection on the faucet that won't allow the faucet to be left on. 3. Pipe the grease trap per manufacturs instructions and plan specfications. 4. Add tempering valves on the public lavatories. Required with a change of tenant.
|